SHEET NOTES:
1.
2.
3.
A
B
13 14
CAP FOR FUTURE CONNECTION TO
SURGICAL TOWER PIPING SYSTEM.
6"CHS
14"HPS
6"PC
6"SAN
4"SAN
2"MA
6"SAN
20"CHS
20"CHR
6"CHR
6"FP
3"NHW
3"CW
5"PC
JJ
5"PC
8"HPS
8"HPS
ALL WORK SHOWN ON SHEET IS PART OF
OPTION BID 0005.
REFER TO CIVIL PLANS FOR PROJECT OPTIONS
AND PHASING PLANS.
COORDINATE SYSTEM SHUT DOWNS WITH
OWNER. SYSTEM TIE-IN WORK SHALL BE DONE
DURING THE OFF SEASON RELATED TO THE
SYSTEM. CHILLED WATER WORK SHALL BE
DONE DURING WINTER MONTHS AND STEAM
AND CONDENSATE WORK SHALL BE DONE
DURING SUMMER MONTHS.
A
B
3" LPS SERVES
BUILDING 5
3"LPS
16"CHS
10"CHR
HH
5"MPS
5"MPS
20"CHR
20"CHS
5"MPS
CHS, CHR AND LPS
PIPES FROM BLDG-6.
CONNECT TO EXISTING PIPING AT THIS
LOCATION. PROVIDE DOUBLE VALVES
ON STEAM MAIN AS INDICATED.
10"SV RISER UP
10"MPS
12"MPS
12"MPS
8"SV
6"SV
10"FP
10"FP
6"FP
6"FP
3/4"CW
ANCHOR PIPING TO EXISTING
CONCRETE STRUCTURE AT THIS
LOCATION. REFER TO F8/M404 FOR
ANCHOR DETAIL.
PIPE GUIDE
C9
C
FF
NO SCALE
C
20"CHS
ROUTE CHILLED WATER LINES
APPROXIMATELY 6" ABOVE FINISH
FLOOR ALONG PATH INDICATED.
20"CHR
PENETRATIONS SHALL BE SEALED
WITH MODULAR OR LINK RUBBER SEAL
OR AS RECOMMENDED PER DIRECT
BURIED PIPING MANUFACTURER.
(TYPICAL)
14"HPS
20"CHR
4"HWR
4"HWS
2"LPC
4"LPS
REFER TO MS-201 SHEET MECHANICAL
SITE PLAN FOR CONTINUATION.
6"PC
HPS
HWR
HWS
PROVIDE NEW STEAM
PRESSURE REDUCING
STATION IN 1/3 AND 2/3
CONFIGURATION. MATCH
EXISTING EQUIPMENT
LOAD OF 1500 LBS/HR,
60PSI INLET, 8 PSI
OUTLET.
14"HPS
20"CHS
6"PC
20"CHR
C9
01-MP101
6"PC
REFER TO MS201 FOR
CONTINUATION.
14"HPS
20" CHR BELOW AND
20" CHS ABOVE.
20"CHR
GG
16"CHS
20"CHS
20"CHR
20"CHS
ENTRANCE VIEW – BUILDING 01 MECH SG182
PRV-E
6"PC
14"HPS
2"LPC
6"CHS
EE'
10"SV
8"SV
8"SV
T
6"CHR
T
6"MPS
6"MPS
4"MPS
6"MPS
4"MPS
EE
01-PRV-1
PIPE GUIDE
PROVIDE DOUBLE GATE VALVES WITH
GLOBE VALVE BYPASS WITH 1" TAP
AND BLEED VALVE BETWEEN GATE
VALVES. TYPICAL FOR ALL DOUBLE
VALVES SHOWN ON STEAM AND
CONDENSATE PIPING.
6"SV
5"LPS
3"HPC
3"HPC
CC
10"MPS (MANIFOLD)
PRV-6E
2"MPS
6"LPS
6"HPS
5"LPS UP
6"CHR
6"CHS
5"MPS
5"LPS
BB
6"MPS
PRV-1E
8"MPS
5" HPS & 2 1/2" PC
UNDERGROUND
The beginning of the document. Download the full file to read on.
Other documents in this bid
- JA (Class) - Interior Finishes Redacted
- JA 01 - Siemens or JCI HVAC BAS Redacted
- JA 02 - JCI Fire Redacted
- JA 03 - JCI ESS Redacted
- JA 04 - Assa Abloy Redacted
- JA 05 - AMAZ Redacted
- Specifications - Volume I
- Specifications - Volume II
- Amendment 1: Submission Requirements and Evaluation Criteria
- Amendment 1
- Amendment 2: Bidding Schedule
- Amendment 2: Specifications Section 01 22 00