Bid document
Updated
A Word document (4.7 MB) attached to Boiler 3 Oxygen Analyzer and Steam Flow Meter, from the Department of Veterans Affairs. Due Oct 26, 2026, 10:00 AM (UTC-5).
File name: 36C24727Q0050 0001_1.docx
The full file is for paid members, or buy this bid alone.
Preview
SUBJECT*
Boiler 3 Oxygen Analyzer and Steam Flow Meter
GENERAL INFORMATION
CONTRACTING OFFICE’S ZIP CODE*
30096
SOLICITATION NUMBER*
36C24727Q0050
RESPONSE DATE/TIME/ZONE
10-26-2026 10:00 am CENTRAL TIME, CHICAGO, USA
ARCHIVE
90 DAYS AFTER THE RESPONSE DATE
RECOVERY ACT FUNDS
N
SET-ASIDE
SDVOSBC
PRODUCT SERVICE CODE*
N045
NAICS CODE*
238220
CONTRACTING OFFICE ADDRESS
Department of Veterans Affairs
VISN 7 Network Contracting Office
3 FL Directors Office
3700 Crestwood Parkway
Duluth GA 30096
POINT OF CONTACT*
Contract Specialist
Sheryl Harris
[email protected]
email only
PLACE OF PERFORMANCE
ADDRESS
Department of Veterans Affairs
Carl Vinson VA Medical Center
1826 Veterans Blvd
Dublin GA
POSTAL CODE
31021
COUNTRY
USA
ADDITIONAL INFORMATION
AGENCY’S URL
URL DESCRIPTION
AGENCY CONTACT’S EMAIL ADDRESS
EMAIL DESCRIPTION
DESCRIPTION
Questions and Answers
36C24727Q0050 Boiler #3 Oxygen Analyzer and Steam Flow Meter RFI Responses Where should the output signals from the new steam flow meter and O2 analyzer terminate? For example, the existing building automation system (BAS), the existing Boiler 3 burner/boiler controls, or a local display only. Burner 3 boiler/burner controls where applicable and local display. Does the government require active O2 trim control to the burner fuel/air ratio, or monitoring and display of the O2 only? Oxygen analyzer must send signals/information to combustion controls to control trim. What is the material of construction for the stack? Is it single or double wall? Stack is double walled. Inside material is steel; outside material is galvanized steel. Stack is 36” D Selkirk Metalbestos Model P.S. Current operating pressure and temperature of the system for boiler #3? Design pressure is 200 psi. Typical operating pressure is 82 psi. Typical operating temperature is about 330 degrees Fahrenheit. What are the available outputs on the physical steam flow meter (e.g., 4-20 mA, Modbus RTU, BACnet MS/TP)? 4-20 mA analog.
Is the flow meter wired directly into an analog terminal block on the CB Hawk, or is it wired directly to the facility’s Building Automation System (BMS)? Steam flow meter is wired into local CB Hawk analog terminal block. Please provide nameplates for the existing oxygen analyzer and steam flow meter. Oxygen analyzer nameplate:
Steam flow meter nameplate:
5. PROJECT NUMBER (if applicable)
CODE
7. ADMINISTERED BY
2. AMENDMENT/MODIFICATION NUMBER
CODE
6. ISSUED BY
8. NAME AND ADDRESS OF CONTRACTOR
4. REQUISITION/PURCHASE REQ. NUMBER
3. EFFECTIVE DATE
The beginning of the document. Download the full file to read on.