September 23, 2025
Kenneth Ballard
Department of Veterans Affairs

RE: Semi- Annual Elevator Inspection Reports- for Garland VA- 2300 Marie Curie Garland, TX 75042
Mr. Ballard,
We are pleased to provide the following elevator inspection reports for all hydraulic and traction elevators located at the Garland VAMC with the exception of units P2 and P14 that were out of service. Please advise when these units will be back in service and we will perform the annual inspections at that time.

ELEVATOR

VIOLATION

P1

A17.1 8.6.1.4.1 MCP's - Provide Fire Logs, Periodic Test Tag A17.1 3.27.1 Repair Emergency phone

P2

Down Unit

P3

A17.1 8.6.1.4.1 MCP's - Provide Fire Logs, Periodic Test Tag A17.1 3.27.1 Repair Emergency phone
A17.1 3.27.3 Repair Fire Phase I light and buzzer

P4

A17.1 8.6.1.4.1 MCP's - Provide Fire Logs, Periodic Test Tag A17.1 3.27.1 Repair Emergency phone
A17.1 2.13 Hoist-way doors shall be self closing (lobby door has broken spirator)

P5

A17.1 8.6.1.4.1 MCP's - Provide Fire Logs, Periodic Test Tag A17.1 3.27.1 Repair Emergency phone
A17.1 3.27.3 Repair Fire Phase I light and buzzer

P6

A17.1 8.6.1.4.1 MCP's - Provide Fire Logs, Periodic Test Tag A17.1 3.27.1 Repair Emergency phone
A17.1 2.27.3 Repair Fire Phase I (no audio indicator in COP)

P7

A17.1 8.6.1.4.1 MCP's - Provide Fire Logs, Periodic Test Tag A17.1 3.27.1 Repair Emergency phone

P8

A17.1 8.6.1.4.1 MCP's - Provide Fire Logs, Periodic Test Tag A17.1 3.27.1 Repair Emergency phone
A17.1 2.14.7.1.3 Repair emergency lighting and alarm

P9

A17.1 8.6.1.4.1 MCP's - Provide Fire Logs, Periodic Test Tag A17.1 3.27.1 Repair Emergency phone

P10

A17.1 8.6.1.4.1 MCP's - Provide Fire Logs, Periodic Test Tag A17.1 3.27.1 Repair Emergency phone

P11

A17.1 8.6.1.4.1 MCP's - Provide Fire Logs, Periodic Test Tag A17.1 3.27.1 Repair Emergency phone
A17.1 2.14.7.1.3 Repair emergency lighting and alarm

P12

A17.1 8.6.1.4.1 MCP's - Provide Fire Logs, Periodic Test Tag A17.1 3.27.1 Repair Emergency phone
A17.1 2.14.5.7 Restricted opening of car doors (repair or replace door restrictor) (front and Rear)

P13

A17.1 8.6.1.4.1 MCP's - Provide Fire Logs, Periodic Test Tag A17.1 3.27.1 Repair Emergency phone
A17.1 2.14.5.7 Restricted opening of car doors (repair or replace door restrictor)
A17.2 5.1.1e No water or oil shall be allowed to accumulate in pit.

P14

Unit Down

Rick Walker Sr.
President, GreenEfficient, Inc.