LOW VOLTAGE POWER CIRCUIT BREAKER

TEST AND

Wilmington VA

PAGE

ADDRESS

1601 Kirkwood Highway ; Wilmington DE 19805

JOB #

861903

USER

Wilmington VA

CUSTOMER

OWNER REPRESENTATIVE

DATE

5/18/2025

TELEPHONE

TEMPERATURE

°C

HUMIDITY

%

MANUFACTURER:

Eaton

BREAKER TYPE:

NGS 50K

FRAME SIZE:

N/A

SENSOR TAPS:

1200

Main Breaker

POSITION

SN /SO NO:

TRIP UNIT TYPE:

1601 Kirkwood Highway

EQPT. LOCATION

Building 143 ( Emergency Gear)

SUBSTATION

MOUNTING:

N/A

FUSE CAT. NO:

N/A

OPS AS FOUND /AS LEFT:

On

On

Description

INSPECTED

CONDITION

CUBICLE AND RACKING DEVICES

Acceptable

C

N/A

N/A

N/A

N/A

GROUND CONNECTION

N/A

N/A

MECHANISM

CONTACT FINGERS

n

LOADING AND ARCING CONTACTS

I-

OVERCURRENT DEV. BATTERY

r

CLEAN/LUBE

D.O.

B.I.

MANUAL/ELECTRIC:

E

CONTROL VOLTAGE CLOSE:

N/A

CONTROL VOLTAGE TRIP:

N/A

Description

INSPECTED

CONDITION

CLEAN/LUBE

ARC CHUTES

J7

Acceptable

C

AUXILIARY DEVICES

I-

N/A

N/A

r

N/A

N/A

Acceptable

C
_J

SETTINGS AS FOUND

LONG TIME PU

X

1200

A =

1200

A

DELAY

DELAY

N/A

PT

0 IN r , OUT aiN N/A

PT

0 IN 0 OUT (.4‘ N/A

DELAY N/A

PT

O IN

C' OUT (4-1P N/A

DELAY

PT

O IN

("N OUT AP N/A

RATING PLUG(R)

1200

SHORT TIME PU

1200

A

(

ON

0 OFF

SENSOR TAP

N/A

INST. PU

N/A

N/A

A

(") ON

OFF

GRD. FLT. PU

N/A

N/A

A

O ON (4.` OFF

DELAY

N/A

1200

A

DELAY

0 ON r

OFF

SETTINGS AS LEFT

LONG TIME PU

1200

X

1200

A =

RATING PLUG(R)

1200

SHORT TIME PU

=

1200

A

SENSOR TAP

Nli,

INST. PU

N/A

=

N/A

A

C' ON r OFF

GRD. FLT. PU

N/A

=

N/A

A

C' ON O OFF

N/A

PRIMARY INJECTION TEST

PHASE A

TEST

CURRENT

MINIMUM

INSTANTANEOUS

N/A

SHORT TIME

N/T

LONG TIME

GROUND FAULT

FUNCTION

TIME BAND / CURRENT

PHASE B

PHASE C

MAXIMUM

AS

FOUND

AS

LEFT

AS

FOUND

AS

LEFT

AS

FOUND

AS

LEFT

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/T

NfT

N/T

N/T

N/T

N/T

N/T

N/T

N/T

N/T

N/T

N/T

N/T

N/T

N/T

N/T

N/T

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

PICK UP

CONTACT RESISTANCE - IN MICRO-OHMS

A
N/A
N/A

BREAKER

FUSE

BREAKER & FUSE

Test Current @

BREAKER

CLOSED

NIT
Phase A - Phase B
NIT

BREAKER

OPEN

COMMENTS:

DEFICIENCIES:

Meg-Ohms N/T

Phase C - Ground

Meg-Ohms N/T

Meg-Ohms
Phase C Line - Load

Meg-Ohms NTT

Cat #NGS312033E, Style: 149r3D04G
Lin b
ae
ker to perform insulation resistance testing. All test results Megger Cal #185627. AEMC Cal # 100343.
While operating- breaker, the breaker would not reset. Recommend repla ng as oon s possible

Form Number:15118, Designed By FM 4/16/2020

Meg-Ohms
Phase C - Phase A

Phase B Line - Load
Meg-Ohms NIT

VDC

Meg-Ohms N/T
Phase B - Phase C

Phase A Line - Load
N/T

1,000

Phase B - Ground
Meg-Ohms N/T

Amps

C
N/A
N/A

MEGGER TEST RESULTS - MEGGER VOLTAGE @

Phase A - Ground

B
N/A
N/A

TESTED BY: BS

Meg-Ohms
acceptable to NETA test standa

LOW VOLTAGE POWER CIRCUIT BREAKER

TEST AND INSPECTION

Wilmington VA
1601 Kirkwood Highway ; Wilmington DE 19805