Incident: 286467
Incident: 286467
Status: Completed

Entered: 8/11/2026 7:21:39 AM

Started: 10/6/2026 4:30:00 AM

Requested: 9/15/2026 12:00:00 AM

Finished: 10/6/2026 8:00:00 AM

Customer ID: C16590
Customer: Cold Regions Research and
Engineering Laboratory
Main Lab

72 Lyme Raod

Hanover, NH 03755

Assigned To: AFROST

Severity: Low - PM

Item: ONAN
Serial Number: E950578362
Product Line: ONGENERAT

Problem Notes
Perform Major PM

Solution Notes
Completed major pm on unit.
Nothing to quote at this time

Parts
Entry Date

Item Number

Description

Quantity

8/11/2026

MAJORPM

Major Planned Service Inspection

1.00

Notes:
10/7/2026

NAPA-3405

Fuel Filter

1.00

Notes:
10/7/2026

NAPA-400060

Coolant Filter

REPLCS WF2076

1.00

Notes:
10/7/2026

NAPA-1970

Oil Filter

1.00

Notes:
10/7/2026

KOH15W40

Oil conventional diesel
Notes:

Signature:

11.00

PM Checklist Results: Maintenance
Task Number: 1 Item #: ONAN

Serial #: E950578362

Inspection Item

Result

Battery Quantity

Battery Type

4d

Battery Date

9/2025

Battery electrolite level

Satisfactory

Specific Gravity

Satisfactory

Static Battery Voltage

24.7

Cranking Battery Voltage

22.9

Battery Connections

Satisfactory

Battery Cables

Satisfactory

Battery Charger DC Voltage

26.2

Battery Charger Fuse

Satisfactory

Engine Oil Leaks

Satisfactory

Engine Coolant Leaks

Satisfactory

Engine Fuel Leaks

Satisfactory

Engine Exhaust Leaks

Satisfactory

DC Controls Connections

Satisfactory

Cooling System Level

Satisfactory

Freeze Proof Protection

Antifreeze Condition

Pass

Cooling system Hoses / Connections

Satisfactory

Radiator

Satisfactory

Water Pump

Satisfactory

Engine Block Heater

Satisfactory

Airflow

Satisfactory

Louvers

Satisfactory

Lube Oil Level

Satisfactory

Lube Oil Condition

Satisfactory

Date Lube Oil Last Changed

10/6/2026

Lube Oil Heater

Satisfactory

Engine Belts

Satisfactory

Engine Starter

Satisfactory

Engine Air Filters

Satisfactory

Engine Breather

Satisfactory

Engine Oil Pressure

Engine Water Temperature

AC Wiring / Connections

Satisfactory

Day Tank Operation

Satisfactory

Main Fuel Tank Level

Satisfactory

Fuel Filters

Satisfactory

Fuel Lift Pump

Satisfactory

Fuel Injection Pump

Satisfactory

Available Load Test

Not Performed

Low Coolant Level Safety Shutdown

Satisfactory

Oil Pressure Safety Shutdown

Satisfactory

Oil Pressure Safety Prewarn

Satisfactory

Hi Water Temp Safety Shutdown

Satisfactory

Hi Water Temp Safety Prewarn

Satisfactory

Over Speed Safety Shutdown

Satisfactory

Over Crank Safety Shutdown

Satisfactory

Low Coolant Temp safety

Satisfactory

Low Battery Voltage Safety

Satisfactory

Generator Circuit Breaker Closed

Satisfactory

Left In "AUTO"