REQUEST FOR QUOTATION

Single-Zone Extended Piping Wall
Mount

PLEASE COMPLETE ALL SECTIONS IN YELLOW:

1. Offeror Information:

Legal Business Name

Contact Name and Title

Address

Email

Phone

UEI

Business Type

▢ Manufacturer ▢ Dealer

Business Size

▢ Large ▢ Small

2. Requirement Details

NSN/Part Number

Single-Zone Extended Piping Wall Mount

Small Business
Set-Aside

Yes
No

Requirement Type

QTY

Requested

DARO

30 days

Generic
Brand Name
Brand Name or Equal

Delivery Zip Code 92135

NAICS

333415

Single-Zone Extended Piping Wall Mount (Qty. 9 EA) – LG P/N KSSAP361A* with the following salient characteristics:

1. Performance

a. Cooling
i. Cooling Capacity (Min~Rated~Max) (Btu/h): 3,070~33,000~34,000 ii. SEER2 – 20.0
iii. EER2 – 10
SEER - Seasonal Energy Efficiency Ratio
EER - Energy Efficiency Ratio

b. Heating
i. Heating Capacity (Min~Rated~Max) (Btu/h): 3,070~35,200~38,900 ii. HSPF2: 8.5
iii. Max. Heating @ Indoor 70°F DB
1. Outdoor 19°F DB / 17°F WB: 30,000 (85%)
2. Outdoor 6°F DB / 5°F WB: 26,000 (74%)

RFQ 47QSSC-27-R-0006

3. Outdoor 1°F DB / 0°F WB: 23,210 (66%)
4. Outdoor -3°F DB / -4°F WB: 21,620 (61%)
HSPF - Heating Seasonal Performance Factor
Cooling Nominal Test Conditions:
Indoor: 80°F DB / 67°F WB
Outdoor: 95°F DB / 75°F WB
Heating Nominal Test Conditions:
Indoor: 70°F DB / 60°F WB
Outdoor: 47°F DB / 43°F WB

2. Electrical

a. Power Supply (V¹/Hz/Ø): 208-230-60/1

b. MOP (A): 30.0

c. MCA (A): 23.0

d. Cooling Rated Amps (A): 15.00
e. Heating Rated Amps (A): 13.20
f. Compressor (A): 15.1
g. Fan Motor (IDU + ODU) (A): 0.5 + 0.4
h. Cooling Power Input (kW) (Min~Rated~Max @95°F) (kW): 0.500~3.300~4.020 i. Heating Power Input (kW) (Min~Rated~Max @47°F) (kW): 0.660~2.933~4.370 MOP – Maximum Overcurrent Protection
MCA – Minimum Circuit Ampacity

3. Piping

a. Liquid Line (in., O.D.): 3./8 Flare
b. Vapor Line (in., O.D.): 5/8 Flare
c. Additional Refrigerant (oz./ft.): 0.32
d. Min. / Max. Pipe Length (ft.)²: 9.8 / 164.0
e. Piping Length (no add’l refrig., ft.): 0.500~3.300~4.020 f. Max. Elevation (ft.): 0.660~2.933~4.370

4. Operating Range

a. Outdoor Unit
i. Cooling (°F DB): 14 ~ 118
ii. Heating (°F WB): -4 ~ +65
b. Indoor Unit
i. Cooling (°F DB): 53 ~ 75
ii. Heating (°F WB): 60 ~ 86

5. System Data

a. Refrigerant Type: R32
b. Refrigerant Control: EEV
c. Refrigerant Charge (lbs.): 4.406
d. ODU Sound Pressure (Cooling / Heating) (±1 dB[A])³: 55/58 e. IDU Sound Pressure
i. Cooling (H/M/L/Sleep) (±1 dB[A])³: 51 / 47 / 43/33

The beginning of the document. Download the full file to read on.