10x10 TransData units

10/20/2026

1.0

Current Transducer Specifications (Item 1):
1.1.1
Number of Electrical Elements: 45
1.1.2
Temperature Range: -20 degrees C to 70 degrees C
1.1.3
Operating Humidity: 0-95%
1.1.4
Power Supply: 100-130V, 60 Hz
1.1.5
Frequency Range: 50-70 Hz
1.1.6
Full Scale Input: 5 Amps
1.1.7
4-20mA DC output
1.1.8
Response Time to 99%: <400 MS
1.1.9
Surge Withstand Capability: 5000V Peak
1.1.10 Accuracy @ 25 degrees C +/- 5 degrees C: +/-0.2% of rated output

1.1.11 Single phase

1.1.12 Calibration Adjustment: +/-10%

1.1.13 Zero (offset) Adjustment: +/- 5%

1.1.14 Utility specified steel enclosure

1.1.15 Standardized mounting footprint

2.0

Voltage Transducer Specifications (Item 2):
2.1.1
Number of electrical elements: 30
2.1.2
Temperature Range: -20 degrees C to 70 degrees C
2.1.3
Operating Humidity: 0-95%
2.1.4
Power Supply: 100-130V, 60 Hz
2.1.5
Frequency Range: 50-70 Hz
2.1.6
Full Scale Input: 5 Amps
2.1.7
4-20mA DC output
2.1.8
Response Time to 99%: <400 MS
2.1.9
Surge Withstand Capability: 5000V Peak
2.1.10 Accuracy @ 25 degrees C +/- 5 degrees C: +/-0.2% of rated output

2.1.11 Single phase

2.1.12 Calibration Adjustment: +/-10%

2.1.13 Zero (offset) Adjustment: +/- 5%

2.1.14 Utility specified steel enclosure

2.1.15 Standardized mounting footprint

3.0

Wattage 2-Element Transducer Specifications (Item 3):
3.1.1
Number of wiring terminals: 10
3.1.2
Temperature Range: -20 deg C to 70 deg C
3.1.3
Operating Humidity: 0-99% non-condensing
3.1.4
Power Supply: 120V, 60 Hz
3.1.5
Frequency Range: 50-70 Hz
3.1.6
Full Scale Input: 5 Amps
3.1.7
4-20mA DC output
3.1.8
Response Time to 99%: <400 MS
3.1.9
Surge Withstand Capability: 5000V Peak
3.1.10 Accuracy @ 25 degrees C +/- 2 deg C: +/-0.1% of rated output

3.1.11 Three phase

3.1.12 Calibration Adjustment: +/-10%

3.1.13 Zero Adjustment: none required

3.1.14 Utility specified steel enclosure

3.1.15
4.0

Standardized mounting footprint

Wattage 2.5-Element Transducer Specifications (Item 4): 4.1.1
Number of wiring terminals: 5
4.1.2
Temperature Range: -20 deg C to 70 deg C
4.1.3
Operating Humidity: 0-99% non-condensing
4.1.4
Power Supply: 120V, 60 Hz
4.1.5
Frequency Range: 50-70 Hz
4.1.6
Full Scale Input: 5 Amps
4.1.7
4-20mA DC output
4.1.8
Response Time to 99%: <400 MS
4.1.9
Surge Withstand Capability: 5000V Peak