DESIGN PACKAGE DEVELOPED BY:
DATA CENTER AND INFRASTRUCTURE ENGINEERING
GENERIC EXTRA SMALL (~780FT2) DATA CENTER DESIGN PACKAGE
FOR MAIN COMPUTER ROOMS (MCRS)
AND OTHER
CAMPUS SUPPORT CENTERS (CSCS)
A
B
C
C
D
D
DATE
SHEET:
SHEET TITLE
ISSUE DATE:
PRINT DATE:
DOC VERSION No:
OF
TITLE
Jun 25, 2021
Sep 21, 2021
1.0
KEVIN GRZELKA, CTDC
MICHAEL JULIAN, RCDD
KELLY BATES, DCIE
CHECKED BY:
Generic Extra Small Data Center Design Package 1.vsd
DESCRIPTION
DESIGNED BY:
FILE:
DRAWING No:
ISSUE:
MARK
GENERIC EXTRA SMALL DATA
CENTER DESIGN PACKAGE
FOR MCRS AND
OTHER CSCS
PROJECT:
ENTERPRISE DATA CENTER AND
INFRASTRUCTURE ENGINEERING
IT Operations and Services
Solution Delivery
Department of Veterans Affairs
A
B
C
D
C
M
J
#
OR
#
TYP
DETAIL NUMBER
TYPICAL THROUGHOUT THIS
SHEET
6 FT WIDE, 8 FT HIGH DOOR, NO CENTER MULLION, FIRE
RESISTANT TO ¾ HOUR OR MORE PER AHJ
3 FT WIDE, 8 FT HIGH DOOR, FIRE RESISTANT TO ¾ HOUR OR
MORE PER AHJ
4'X 8' AC GRADE ¾” TRADE SIZE PLYWOOD BACKBOARD
PAINTED HIGH-GLOSS WHITE WITH TWO COATS OF FIRE
RESISTANT PAINT FOR SERVICE PROVIDER / SECURITY /
VIDEO / ET CETERA
NEW WALL
DEMO WALL
ARCHITECTURAL
MODULAR UPS CABINET (POWER MODULES, BATTERIES,
POWER PANELS)
POWER BUSWAY WITH METERED HEADEND FOR B SIDE
POWER DISTRIBUTION
POWER BUSWAY WITH METERED HEADEND FOR A SIDE
POWER DISTRIBUTION
LED LIGHTING
FIXED CAMERA, PAN/TILT/ZOOM, PASSIVE INFRARED
CAMERA - DUAL TECHNOLOGY”
PIV ENABLED TWO-FACTOR AUTHENTICATION KEYPAD
CEILING MOUNTED MOTION SENSOR (LOCATIONS AS
REQUIRED FOR FULL ROOM COVERAGE)
MOTION SENSOR LIGHT SWITCH
TYPICAL UNSWITCHED 110 VOLT, 20 AMP DUPLEX
CONVENIENCE OUTLET
POWER BUSWAY TAP WITH DUAL BREAKER AND TWO 3'
DROP CORDS WITH L21-20R FOR HIGH DENSITY CABINETS
POWER BUSWAY TAP WITH SINGLE BREAKER 3' DROP
CORD WITH L21-20R FOR STANDARD-DENSITY CABINETS
POWER JUNCTION BOX FOR 60A CONNECTION
OVERHEAD POWER DROP CORD WITH L21-30 RECEPTACLE
OVERHEAD POWER DROP CORD WITH L21-20 RECEPTACLE
ELECTRICAL SERVICE PANEL
#
TYP
#
LEGEND
WIRE MESH CABLE TRAY SIZE COMMENSURATE WITH
REQUIREMENTS
BONDING BUSBAR
DETAIL NUMBER
ELECTRICAL
SLEEVE WITH BUSHING FIRESTOP AND INNERDUCT FOR
FIBER
SLEEVE OR CONDUIT WITH BUSHING FIRESTOP AND
INNERDUCT FOR FIBER
ADDITIONAL SPLIT PACKAGE AIR CONDITIONER OR LARGER
UNIT TO REJECT HEAT FROM ADDITIONAL RACKS (17,000
BTU PER TELECOMMUNICATIONS RACK)
AC
REQUIRED CLEARANCE AROUND CRACS
COMPUTER ROOM AIR CONDITIONER (SEE COMPUTATIONAL
FLUID DYNAMICS REPORT FOR SIZING)
RETURN AIR DUCT
COLD AISLE CONTAINMENT (PVC CURTAIN)
STANDARD 25% OPEN PERFORATED FLOOR TILE
MECHANICAL
TELECOMMUNICATIONS CABINET, 7' HIGH, 45U, 40"X48"
(NOMINAL), SQUARE PUNCHED RAIL, SINGLE
The beginning of the document. Download the full file to read on.
Other documents in this bid
- Global RLP Template R100 - VA Version Macon
- No Proposal Market Response Form
- Pre-Bid Conference Registration Form
- Global Lease Template L100 - VA Version
- 04A - Exhibit Lease - Broker Project
- 04B - Lease Exhibit - New Construction
- 04C - Exhibit Lease - Prospectus
- Agency Specific Requirements ASR - Cover Page
- 05A PFD FY25 MACON GA HCC 2026.07.29
- 05A04 Appendix A.4 VA CBOC Info Transp Sys Specifications 5 29 2025
- 05A05 Appendix A.5 VA Security Requirements FSL Level II
- 05A06 Appendix A.6 VA Leased CBOC Standard Layout Guide 10 29 25