Computational Fluid Dynamics (CFD)
Simulation - Extra Small Computer Room Rectangle Version

This report contains the results and images from a CFD simulation. It shows the performance of the current cooling system in this representation of a generic extra small computer room for use within VA.

Data Center & Infrastructure Engineering
Solution Delivery, DevSecOps, OIT

Geometry and Objects
Data Center Dimensions
Item

Value

Floor Length

20.0 ft

Floor Width

39.5 ft

Tile Size

24.0 inch

UF Plenum Height

0.0 inch

Real Ceiling Height

12.0 ft

Object Count
Object

Count

Downflow CRACs

Server Racks

Hot Boxes

Vertical Partitions

Horizontal Partitions

Downflow CRACs by Style
Downflow CRAC Style

Total Units

Failed Units

Total Airflow (CFM)

Nominal Cooling (Ton)

Nominal Cooling (kW)

Liebert DS053AS/AD/DS/DD

8,000

15.1

53.2

Racks by Style
Rack Style

Total Racks

Turned Off

Total Heat Load (kW)

Total Airflow (CFM)

CPI TeraFrame 60 cm x 110 cm x 45 U (Ducted)

30.0

4,731

CPI TeraFrame NF8N with Chimney

11.2

1,766

Heat Load/Cooling Airflow
Total Heat Load and Airflow
Item

Value

Net Floor Area

742 sq ft

Heat Load Density

61.2 W/sq ft

Total Heat Load

45.5 kW

Total Airflow Demand

7,497 CFM

Total Airflow Supplied

8,000 CFM

Cooling Airflow Supplied
Source

Value

Downflow CRACs

8,000 CFM

Special CRACs

0.0 CFM

Upflow CRACs

0.0 CFM

In-Row Coolers

0.0 CFM

Overhead Coolers

0.0 CFM

Spot Coolers

0.0 CFM

UF Vents (Net)

0.0 CFM

AF Inlet Vents

0.0 CFM

Summary of AF Results
Total Heat Load and Cooling
Item

Value

Total Airflow Demand

7,497 CFM

Total Airflow Supply

8,000 CFM

Total Heat Load

45.5 kW

Cooling by Cooling Units

45.5 kW

Heat Loads and Cooling Achieved
Item

kW

Ton

Server Rack Heat Load

41.2

11.7

Hot Box Heat Load

4.26

1.21

Cooling by Downflow CRACs

45.5

12.9

Cooling by Upflow CRACs

0.0

0.0

Cooling by RDHx

0.0

0.0

Cooling by In-Row Coolers

0.0

0.0

Cooling by Overhead Coolers

0.0

0.0

Cooling by Spot Coolers

0.0

0.0

Cooling by Inlet Vents

0.0

0.0

Rack Temperature Results
Rack Statistics
Range of Max Inlet Temp

Number of Racks

Above 80 F

Between 75 F and 80 F

Between 70 F and 75 F

Below 70 F

Hot Boxes are included

Rack Temperatures in Detail
No.

Rack or HotBox Name

Xref

Yref

Heat Load

Nominal Airflow

Actual Airflow

TinMax

ToutMax

Tbot_F

Tmid_F

Ttop_F

Row 2 - HDA A_1

7.0

6.1

2.80

67.8

78.5

67.2

67.6

67.7

Row 2 - HDA A

10.4

6.1

2.80

68.6

79.9

67.4

67.7

67.8

Row 2 - Rack 8 SD

13.8

6.0

5.00

69.2

86.8

67.5

68.0

68.7

Row 2 - Rack 9 SD

15.8

6.0

5.00

69.0

87.5

67.8

67.9

68.5

Row 2 - Rack 10 SD

17.8

6.0

5.00

68.7

88.0

67.9

67.7

68.2

Row 2 - Rack 3 SD

19.8

6.0

5.00

68.2

88.1

67.9

67.7

67.9

Row 2 - Rack 1 SD

21.8

6.0

5.00

68.0

88.5

67.9

67.7

The beginning of the document. Download the full file to read on.