Home / Cannon AFB - 4625 Boiler / Document

Attachment 1: Salient Characterisitcs

Updated

A PDF document (136 KB) attached to Cannon AFB - 4625 Boiler, from the Department of the Air Force. Due Nov 5, 2026, 3:00 PM (UTC-7).

File name: Attachment 1 - Salient Characterisitcs.pdf

Download the full documentSee the bid

The full file is for paid members, or buy this bid alone.

Preview

ARMOR® WATER HEATER PRODUCT SUMMARY

(AWH) 400,000 - 1,000,000 BTU/HR

AWH0400

AWH0500

AWH0650

AWH0800

AWH1000

WATER

GALLON CAPACITY

4.4

4.9

6.2

7.3

8.8

HEATING SURFACE (SQ. FT.)

34.80

39.10

52.20

60.90

75.40

WATER CONNECTIONS

2"

2"

2"

2"

2-1/2"

DRAIN

3/4”

3/4”

3/4”

3/4”

3/4”

WATER FLOW RATE (GPM)

HEAD LOSS (FT. OF HD.)

MAX. WORKING PRESSURE (PSI)

MAX. WATER HARDNESS (GRAINS)

GPH @ 70°F RISE

1103

1358

1695

GPH @ 100°F RISE

1187

GPH @ 140°F RISE

# OF RELIEF VALVES

RELIEF VALVE SIZE

3/4"

3/4"

3/4"

3/4"

3/4"

RELIEF VALVE RATING (MBH)

1,912

1,912

1,912

1,912

1,912

RELIEF VALVE PRESSURE RATING (PSI)

RELIEF VALVE TEMPERATURE RATING (°F)

GAS

INLET CONNECTION

1"

1"

1-1/4"

1-1/4"

1-1/4"

MAX. INLET PRESSURE, NAT

14.0” w.c.

14.0” w.c.

14.0” w.c.

14.0” w.c.

14.0” w.c.

MIN. INLET PRESSURE, NAT

4.0” w.c.

4.0” w.c.

4.0” w.c.

4.0” w.c.

4.0” w.c.

MAX. INLET PRESSURE, LP

14.0” w.c.

14.0” w.c.

14.0” w.c.

14.0” w.c.

14.0” w.c.

MIN. INLET PRESSURE, LP

BTU/HR INPUT

8.0” w.c.
399,000

8.0” w.c.
500,000

8.0” w.c.
650,000

8.0” w.c.
800,000

8.0” w.c.
999,000

120V / 1ø

120V / 1ø

120V / 1ø

120V / 1ø

120V / 1ø

ELECTRICAL

VOLTAGE & PHASE / HEATER

AMPS / HEATER

3.0

3.1

3.3

4.3

6.6

120V / 1ø

120V / 1ø

120V / 1ø

120V / 1ø

120V / 1ø

AMPS / PUMP

3.5

3.5

3.5

5.1

5.1

TOTAL AMPS / HEATER & PUMP

VOLTAGE / CONTROL

6.5
24V

6.6
24V

6.8
24V

9.4
24V

11.7
24V

HEIGHT

45"

45"

45"

45"

45"

WIDTH

DEPTH

24"
30-1/2"

24"
30-1/2"

24"
41"

24"
41"

24"
48"

FRONT

24"

24"

24"

24"

24"

BACK

24"

24"

24"

24"

24"

RIGHT SIDE

0"

0"

0"

0"

0"

LEFT SIDE

TOP

0"
24"

0"
24"

0"
24"

0"
24"

0"
24"

4"

4"

6"

6"

6"

VOLTAGE & PHASE / PUMP

DIMENSIONS

SERVICE CLEARANCES

DIRECT VENTING

VENT CONNECTION SIZE

AIR INTAKE CONNECTION SIZE

4"

4"

4"

4"

6"

VENT CATEGORY

IV

IV

IV

IV

IV

VENT MATERIAL (all models)

PVC / CPVC / Polypropylene / Stainless Steel

Lochinvar, LLC • 300 Maddox Simpson Pkwy • Lebanon, TN 37090 • 615-889-8900 / Fax: 615-547-1000 www.Lochinvar.com
AWH-PS-03 Page 1

01/21 Printed in U.S.A.

The beginning of the document. Download the full file to read on.