Attachment B - Statement of Work Lyons VAMC Elevators Repair Bldgs 6 and 53
Updated
A Word document (60 KB) attached to 561A4-25-500 Elevator Upgrade & Modernization Repairs at VA NJ HCS Lyons Buildings 6 & 53, from the Department of Veterans Affairs. Due Oct 29, 2026, 1:00 PM (UTC-4).
File name: Attachment B - SOW_Lyons VAMC Elevators Repair Bldgs 6 and 53.docx
The full file is for paid members, or buy this bid alone.
Preview
Emergency Elevator Replacement Buildings 6 and 53
Lyons VAMC
Project No. 561A4-25-500
Project Scope of Work:
Passenger Elevators in buildings 6 and 53 are down and unable to be repaired due to age and availability of parts. This project is to upgrade and modernize the elevators in both patient buildings (6 and 53). Elevators included in the Scope of the projects are Building 6 P1 and Building 53 elevators S1, P1 and P2. Contractor is responsible to provide labor, materials and supervision to accomplish the following and meet agency and facility needs:
Building 6 P1:
Controllers - Furnish and install a new, non-proprietary and universally serviceable microprocessor based solid state selective collective control system. This system provides smooth acceleration and deceleration of the car. Provide an associated, non-proprietary drive for optimum motor control. The new system will contain all Fire Recall Features and Door Lock Monitoring as required by code.
Machine – Remove existing Machine and replace with new geared machine.
Car Operating Panel (COP) – Furnish and install new car operating panel. COP will include a series of push buttons numbered to correspond to the landings served. The panel will have an emergency stop switch, alarm button, fan and light switch, independent switch, emergency light, emergency phone and braille markings.
Hall Fixtures – Furnish and install new hall fixtures at all landings. Hall fixtures will have an up and down button at intermediate landings and a single button at the terminal landings. The Lobby landing will have a key switch for fire service operation. Hall fixtures will be installed at ADA compliant height.
Shaft Wiring – Furnish and install new shaft wiring from Mechanical room to Elevator Pit. Existing wiring will be removed and replaced with all new wiring for the proper operation of the equipment and shall meet all code requirements. All conductors are to be run in conduit or metal wire-way as required and shall be installed in an orderly manner. Flexible metal conduits may be used for short runs between equipment and risers. The existing conduits may be retained pending the condition. All wiring shall test free from short circuits or grounds and the resistance to ground.
Car Door Operator – Furnish and install new, non-proprietary, heavy duty door operator, header, track and hangers.
Interior Cab – Upgrade existing cab interior, if required furnish one set of custom-made protective padding per elevator.
Rope Gripper – Furnish and install new rope gripper according to codes. Including the addition of a secondary brake device to comply with current code and provide a backup brake system in the event that the primary brake system fails.
The beginning of the document. Download the full file to read on.