The Department of Veterans Affairs, James A. Haley VA Medical Center is currently seeking information from any Service Disabled Veteran-owned Small Business (SDVOSB), Veteran-owned Small Business (VOSB), or Small Business (SB) vendors that can provide the following service.
SCOPE OF WORK:
The Contractor shall provide all labor, travel, parts, materials, transportation, equipment, tools, training, supplies, management and supervision to perform circuit tracing and documenting electrical circuits within the critical and non-critical areas of Building 1.
1. Period of Performance:
The period of performance for this contract 365 days from the Kickoff meeting or the Notice to proceed from the Contracting Officer. Government is aware that scheduling may be difficult at times and an extension may be needed. Contractor will notify the COR, and an extension can consist of Month-by-Month basis (up to 12 months). Tracing will include not limited to:
Safely trace and document electrical circuits feeding hospital departments, including critical care areas. Ensure accurate identification of power sources for all outlets, devices, lighting, and life safety systems. Locate/trace electrical panels throughout building
Label panels, breakers, and field devices to support fast emergency response and future maintenance. Produce comprehensive documentation in support of NFPA 99, NFPA 70 (NEC), and The Joint Commission requirements. Labeling panel schedule to reflect panel locations/line/loads. Determine amperage/voltage draw of panel loads.
Ensure panel is following hospital codes/regulations
Contractor shall apply compliant, durables labels to:
Panelboard and breakers
Device faceplates (outlets, switches)
Subpanels and junction boxes
Include power source panel and circuit number on each label. Emergency power circuits will be labeled with distinct color codes or markings.
Summary Report:
A comprehensive report including findings, panel schedules, and recommendations will be furnished after completion of work if applicable. Contractor shall Develop detailed circuit maps and panel schedules. Identify emergency vs normal power sources. Document any undocumented circuits, discrepancies, or safety issues. Submit digital and hard copy reports in a facility-approved format to the VA within 7 days of completion. Information shown in the report shall be as following: Company’s name, addresses, telephone, & FAX numbers.
Name and signature of contractors who perform the Circuit Tracing.