L STYLE TYPE RP

19" RACK MOUNTING

ANGLES

REFER TO NAMEPLATE

SCHEDULE

XXX
XXX

L STYLE TYPE RP

19" RACK MOUNTING

ANGLES

INSET DINRAIL

MOUNT

NEMA 4X STAINLESS

STEEL ENCLOSURE

60"

FIBER PATCH PANEL 2U FIBER

PATCH PANEL 24 STRAND

SINGLEMODE FIBER OPTICS, AS

REQUIRED

SWING

OUT

DOOR

COMM EQUIPMENT

AS REQUIRED

SWING

OUT

DOOR

FIBER PATCH PANEL 6U FIBER PATCH

PANEL 144 STRAND SINGLMODE FIBER

OPTICS, AS REQUIRED

HOUSEKEEPING

PAD
003S501

FINISHED

GRADE

24"

INSET DINRAIL MOUNT

MIN 24"

CONCRETE

FOUNDATION

36"

90-DEGREE BEND WITH

MIN. 60" RADIUS

7-WAY

MICRODUCT

FIBER OPTIC PATCH PANEL (FOPP##)

FRONT EXTERIOR ELEVATION

009Y501

009Y501

NOT TO SCALE

FIBER OPTIC PATCH PANEL (FOPP##)

SIDE EXTERIOR ELEVATION

009Y501

NOT TO SCALE

FIBER OPTIC PATCH PANEL (FOPP##)

FRONT INTERIOR ELEVATION

NOT TO SCALE

NAMEPLATE SCHEDULE

LINE 1

1/4" STEEL HARDWARE CLOTH

TO DISCOURAGE RODENT

ACTIVITY

MFG WATERPROOF MICRODUCT

CONNECTORS

FOPP61

FOPP91

LINE 2

ROARING SPRINGS FIELD OH/UG ROARING SPRINGS PUMPHOUSE VISITOR CENTER OH/UG

GENERATOR BUILDING

LINE 3

FIBER OPTIC PATCH PANEL 51

FIBER OPTIC PATCH PANEL 91

FIBER OPTIC PATCH PANEL 52

FIBER OPTIC PATCH PANEL 61

4'x3'x3'

PULLBOX

4'
2"
24"

18"

FINISHED

GROUND

WARNING

TAPE (TYP)

7-WAY

MICRODUCT

4" RIGID CONDUIT IF

EXPOSED OR

SHOWN ON PLANS

SEAL TO KEEP

OUT RODENTS

°

7-WAY

MICRODUCT

°

36" STRAIGHT

(TYP)

CLAMP

60" BEND

RADIUS

(MIN)
(TYP)

TRACER WIRE

12" GRAVEL BASE

5/8" COPPER

GROUNDING ROD

NOTE:

1. SEAL MICRODUCT TO JACKET TO MINIMIZE WATER OR FOREIGN BODY INTRUSION. 2. MATCH INNERDUCT COLOR FOR JUNCTIONS.

A/E FIRM

4/27/2026 12:06:19 PM

Autodesk Docs://10350545_NPS_GRCA_N_Rim_Utility_2026/10350545_000_GENERAL.rvt

FOPP52

PULL BOX LID

SCREENED NATIVE

BACKFILL

COIL ENOUGH TRACER WIRE TO

REACH 12" ABOVE BOX

FOPP51

009Y501

MICRODUCT PULL BOX

NOT TO SCALE

DESIGNED:

PRIME:

J. BRAINARD

HDR ENGINEERING, INC.

PM: MATTHEW

GOUGH

DENVER,
CO 80202

P. KEMPF

DENVER, CO

TECH. REVIEW:

K CHANDRA

DATE:

MAY 2026

SUB SHEET NO.

Y501

TITLE OF SHEET

DRAWING NO.

GENERAL

182752

INSTRUMENTATION DETAILS

- FIBER

PMIS/PKG NO.

318719

SHEET

NORTH RIM - GRAND CANYON NATIONAL PARK

OF

LIQUID-TIGHT FLEXIBLE

METALLIC CONDUIT (NOTE 1)

TO NEMA 4X 316 SST

JUNCTION BOX

CONDUIT TO

INSTRUMENT

LB CONDULET

BUSHING WELDED TO

BLIND FLANGE

DRILL 6" BLIND FLANGE

FOR 1" BUSHING

BLIND FLANGE

NOTE 5

PRESSURE GAUGE

ON

1/4" FLUSHING CONNECTION

W/GAUGE COCK AND 1/4" NPT x 3/4"

FEMALE HOSE THREAD ADAPTER

6" FLANGE

TOP OF TANK

316 SST J-HOOK

TANK NOZZLE

PRESSURE SWITCH/TRANSMITTER

1/2" NPT FEMALE CONNECTION

FOR PRESSURE SENSOR

1/2" BALL VALVE

DIAPHRAGM SEAL

SUBMERSIBLE

CABLE (NOTE 2)

SEE NOTES 1, 2 & 3

1/2" NIPPLE