Drawing
Updated
A PDF document (464 KB) attached to 620-26-206 Asbestos Abatement, from the Department of Veterans Affairs. Due Nov 20, 2026, 1:00 PM (UTC-5).
File name: Drawing MR-003-02-PTR-HA101.pdf
The full file is for paid members, or buy this bid alone.
Preview
UP
N.T.S.
KEY LAYOUT
APPROXIMATE
LOCATION OF WASTE
DUMPSTER PER VA
APPROVAL
ACCESS DOOR SHALL BE LOCKED AND A CRITICAL
BARRIER INSTALLED ON CORRIDOR SIDE OF DOOR.
THE CRITICAL BARRIER CONSTRUCTION
SHALL COMPLY WITH APPLICABLE REGULATIONS.
W
N
S
E
N.T.S.
SUPPLY DUCTS
EITHER KEEP
RUNNING OR
COVER WHEN NOT
RUNNING TO KEEP
DUST OUT.
MONTHLY
CHANGED HEPA
FILTER
HEPA NEGATIVE
AIR UNIT
FLEX
DUCT
WEEKLY
CHANGED OR
MORE AS
NEEDED
TAPE ALL
PRE-FILTER
SERVICES
TO PROTECT
AGAINST
CONTAMINATION
E
A
O
V
EXISTING WALLS USED
AS BARRIERS SHALL
HAVE ALL
PENETRATIONS
VERIFIED AND SEALED
BEFORE
CONSTRUCTIONS
STARTS
DOORS AT FIRE RATED
BARRIER TO BE 45 MIN. RATED
AND BE SELF-CLOSING AND
SELF-LATCHING
FIRE EXTINGUISHER ON
PORTABLE FLOOR
BRACKET (SHALL
REQUIRE MORE THAN
ONE.)
EXISTING WALLS USED
AS BARRIERS SHALL
HAVE ALL
PENETRATIONS
VERIFIED AND SEALED
BEFORE
CONSTRUCTIONS
STARTS
FIRE EXTINGUISHER ON
PORTABLE FLOOR
BRACKET (SHALL
REQUIRE MORE THAN
ONE.)
PRESSURE INDICATOR SHALL
BE AT 0.03-INCH WATER GAUGE
OR GREATER (VERIFY DAILY). IF
NOT VERIFY ALL OPENING SUCH
AS DOOR ARE CLOSED AND/OR
CHANGE NEGATIVE AIR
PRE-FILTER.
DOOR TO BE SELF-CLOSING AND
SELF-LATCHING - 45 MIN. PER
NFPA
HEPA VACUUM OR
DISPOSABLE COVERALLS
DISPENSER & COLLECTION
BIN.
SHOE COVER DISPENSER &
COLLECTION BIN.
PRESSURE INDICATOR SHALL
BE AT 0.03-INCH WATER GAUGE
OR GREATER (VERIFY DAILY). IF
NOT VERIFY ALL OPENING SUCH
AS DOOR ARE CLOSED AND/OR
CHANGE NEGATIVE AIR
PRE-FILTER.
PUBLIC
AREA
CONSTRUCTION
ANTE ROOM
CONSTRUCTION
AREA
PROVIDE STICKY MATS (CHANGED
END OF EVERY SHIFT OR MORE IF
NECESSARY TO MAINTAIN
CLEANLINESS).
PROVIDE STICKY MATS (CHANGED
END OF EVERY SHIFT OR MORE IF
NECESSARY TO MAINTAIN
CLEANLINESS).
CONSTRUCTION
AREA
PUBLIC
AREA
TYPICAL ANTE ROOM
ANTE ROOM BARRIERS
SAME AS CONSTRUCTION
BARRIERS OR PREFAB
UNIT
WEEKLY
CHANGED OR
MORE AS
NEEDED
PRE-FILTER
HEPA NEGATIVE AIR
UNIT
MONTHLY
CHANGED HEPA
FILTER
N.T.S.
TYPICAL CONSTRUCTION LAYOUT-