Drawing - Electrical
Updated
A PDF document (1.7 MB) attached to R-410A LEAK DETECTORS (Bldgs 750, 751 & 768), from the Department of the Air Force. Due Nov 2, 2026, 9:00 AM (UTC-6).
File name: Drawing - Electrical.pdf
The full file is for paid members, or buy this bid alone.
Preview
Location: UNIT 126
Mounting: RECESSED NEMA1
Mains Rating: 125 A MLO
GENERAL NOTES
PANELBOARD: LC12
P
VOLTAGE: 120\208V 1Ø
A.I.C. RATING: 10,000 AMPS SYMMETRICAL
SPECIAL:
A. REFER TO E-001 FOR ELECTRICAL SYMBOLS LEGEND, ABBREVIATIONS, NOTES, AND APPLICABLE CODES.
B. REFER TO E-002 FOR ELECTRICAL ONE-LINE DIAGRAM.
Supply From: MSB
US Army Corps
of Engineers ®
BKR
CKT
A
1560
1083
1215 1263
1944 1331
1944
TOTAL LOAD:
12 kVA
108 A
TOTAL AMPS:
CONNECTED
DEMAND
0 VA
0.00%
333 VA
100.00%
717 VA
125.00%
125 VA
125.00%
9780 VA
100.00%
9824 VA
40.00%
ELECTRIC RANGE
N
*~REFRIGERATOR
*~MICROWAVE
*~RANGE HOOD
*~KITCHEN RCPT
*LIVING RM RCPT/LTG
*SMOKE DETECTORS
*BDRM 1 FRIDGE/MICRO RCPT
*BDRM 2 FRIDGE/MICRO RCPT
*BDRM 3 FRIDGE/MICRO RCPT
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
M
L
LOAD CLASSIFICATION
Fire Alarm
HVAC
Lighting
Motor
Receptacle
SPEC
K
POLES
B
1560
1263
1331
1944
1331
9 kVA
87 A
ESTIMATED
0 VA
333 VA
897 VA
156 VA
9780 VA
3930 VA
CKT
POLES
BKR
FCU/BS
*BDRM 1 BATH RCPT
*BDRM 2/3 BATH RCPT
*BDRM 1 RCPT/LTG
*BDRM 2 RCPT/LTG
*BDRM 3 RCPT/LTG
*A/C UNIT - BDRM 1
*A/C UNIT - BDRM 2
*A/C UNIT - BDRM 3
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
D. REFER TO E-601 FOR ELECTRICAL EQUIPMENT SCHEDULES.
LOAD DESCRIPTION
E. REFER TO E-602 AND E-603 FOR ELECTRICAL PANEL SCHEDULES.
F. REFER TO EP401 THRU EP403 FOR ENLARGED TYPICAL UNIT POWER
PLANS.
G. REFER TO EP404 THRU EP406 FOR ENLARGED COMMON AREA POWER
PLANS.
H. PROVIDE ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION IN DORMITORY
UNITS PER NEC 210.12 (B) WHICH STATES ALL 120-VOLT, SINGLE-PHASE, 15AND 2O- AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS AND DEVICES INSTALLED IN DORMITORY UNIT BEDROOMS, LIVING ROOMS, HALLWAYS,
CLOSETS, BATHROOMS, AND SIMILAR ROOMS SHALL BE PROTECTED BY
ANY OF THE MEANS DESCRIBED IN 210.12(A)(1) THROUGH (6).
ELECTRICAL POWER KEYED NOTES
PANEL TOTALS
1. PROVIDE 208V, 30A RECEPTACLE (NEMA 10-30R) FOR GFGI ELECTRIC
OVEN RANGE. NEMA 10-30P FOR ELECTRIC OVEN RANGE MUST BE
SPECIFIED.
CONNECTED LOAD: 20697 VA
ESTIMATED DEMAND: 15004 VA
CONNECTED CURRENT: 100 A
EST. DEMAND CURRENT: 72 A
2. PROVIDE 120V, 20A RECEPTACLE IN CABINET SPACE ABOVE RANGE FOR
RANGE HOOD POWER CHORD CONNECTION.
ASI 24
ASI 22
ASI 10
DESCRIPTION
LOAD DESCRIPTION
6/9/23
5/5/23
DEC 2022
DATE
C. REFER TO E-003 FOR ELECTRICAL SITE PLAN.
MARK
NOTES:
* = AFCI CIRCUIT BREAKER
~ = GFCI CIRCUIT BREAKER
*~ = COMBINATION AFCI/GFCI CIRCUIT BREAKER
ISSUE DATE:
06/29/2022
SOLICITATION NO.:
The beginning of the document. Download the full file to read on.