Location: UNIT 126
Mounting: RECESSED NEMA1
Mains Rating: 125 A MLO

GENERAL NOTES

PANELBOARD: LC12

P

VOLTAGE: 120\208V 1Ø

A.I.C. RATING: 10,000 AMPS SYMMETRICAL

SPECIAL:

A. REFER TO E-001 FOR ELECTRICAL SYMBOLS LEGEND, ABBREVIATIONS, NOTES, AND APPLICABLE CODES.
B. REFER TO E-002 FOR ELECTRICAL ONE-LINE DIAGRAM.

Supply From: MSB

US Army Corps
of Engineers ®

BKR

CKT
A
1560
1083
1215 1263
1944 1331
1944

TOTAL LOAD:

12 kVA

108 A

TOTAL AMPS:

CONNECTED

DEMAND

0 VA

0.00%
333 VA
100.00%
717 VA
125.00%
125 VA
125.00%
9780 VA
100.00%
9824 VA
40.00%

ELECTRIC RANGE

N

*~REFRIGERATOR

*~MICROWAVE

*~RANGE HOOD

*~KITCHEN RCPT

*LIVING RM RCPT/LTG

*SMOKE DETECTORS

*BDRM 1 FRIDGE/MICRO RCPT

*BDRM 2 FRIDGE/MICRO RCPT

*BDRM 3 FRIDGE/MICRO RCPT

Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare

M

L

LOAD CLASSIFICATION

Fire Alarm

HVAC

Lighting
Motor
Receptacle

SPEC

K

POLES

B
1560

1263

1331

1944

1331

9 kVA

87 A

ESTIMATED

0 VA

333 VA
897 VA
156 VA
9780 VA
3930 VA

CKT

POLES

BKR

FCU/BS

*BDRM 1 BATH RCPT

*BDRM 2/3 BATH RCPT

*BDRM 1 RCPT/LTG

*BDRM 2 RCPT/LTG

*BDRM 3 RCPT/LTG

*A/C UNIT - BDRM 1

*A/C UNIT - BDRM 2

*A/C UNIT - BDRM 3

Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare

D. REFER TO E-601 FOR ELECTRICAL EQUIPMENT SCHEDULES.

LOAD DESCRIPTION

E. REFER TO E-602 AND E-603 FOR ELECTRICAL PANEL SCHEDULES.

F. REFER TO EP401 THRU EP403 FOR ENLARGED TYPICAL UNIT POWER

PLANS.

G. REFER TO EP404 THRU EP406 FOR ENLARGED COMMON AREA POWER

PLANS.

H. PROVIDE ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION IN DORMITORY

UNITS PER NEC 210.12 (B) WHICH STATES ALL 120-VOLT, SINGLE-PHASE, 15AND 2O- AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS AND DEVICES INSTALLED IN DORMITORY UNIT BEDROOMS, LIVING ROOMS, HALLWAYS,

CLOSETS, BATHROOMS, AND SIMILAR ROOMS SHALL BE PROTECTED BY

ANY OF THE MEANS DESCRIBED IN 210.12(A)(1) THROUGH (6).

ELECTRICAL POWER KEYED NOTES

PANEL TOTALS

1. PROVIDE 208V, 30A RECEPTACLE (NEMA 10-30R) FOR GFGI ELECTRIC

OVEN RANGE. NEMA 10-30P FOR ELECTRIC OVEN RANGE MUST BE

SPECIFIED.

CONNECTED LOAD: 20697 VA

ESTIMATED DEMAND: 15004 VA

CONNECTED CURRENT: 100 A

EST. DEMAND CURRENT: 72 A

2. PROVIDE 120V, 20A RECEPTACLE IN CABINET SPACE ABOVE RANGE FOR

RANGE HOOD POWER CHORD CONNECTION.

ASI 24
ASI 22
ASI 10

DESCRIPTION

LOAD DESCRIPTION

6/9/23
5/5/23
DEC 2022

DATE

C. REFER TO E-003 FOR ELECTRICAL SITE PLAN.

MARK

NOTES:

* = AFCI CIRCUIT BREAKER

~ = GFCI CIRCUIT BREAKER

*~ = COMBINATION AFCI/GFCI CIRCUIT BREAKER

ISSUE DATE:

06/29/2022

SOLICITATION NO.:

The beginning of the document. Download the full file to read on.