Emergency Lighting Inverter Systems - CLIN Salient Characteristics

CLIN 0001

Basis of Design: Myers 2-D-4-S-BD2005-ND2005-S
Characteristic
Requirement
Capacity
Approximately 10,000 VA/W
Input
277/480 VAC, 3-phase, 60 Hz, 4-wire plus ground
Output
277/480 VAC, 3-phase, 60 Hz, 4-wire plus ground
Minimum battery runtime

90 minutes

Battery type
VRLA (Valve Regulated Lead Acid)
Configuration
Two-cabinet system
Output breakers
Five (5) 20A, single-pole, normally ON output breakers; Five (5) 20A, single-pole, normally OFF output breakers Includes
Summary dry contacts for remote monitoring and alarm notification Transfer design
Fast-transfer design suitable for emergency lighting applications Listing
UL listed for emergency lighting service
Condition
Furnished as new equipment

CLIN 0002

Basis of Design: Myers 2-D-1-S-BD2002-ND2002-S
Characteristic
Requirement
Capacity
Approximately 4,800 VA/W
Input
277/480 VAC, 3-phase, 60 Hz, 4-wire plus ground
Output
277/480 VAC, 3-phase, 60 Hz, 4-wire plus ground
Minimum battery runtime

90 minutes

Battery type
VRLA (Valve Regulated Lead Acid)
Configuration
Two-cabinet system
Output breakers
Two (2) 20A, single-pole, normally ON output breakers; Two (2) 20A, single-pole, normally OFF output breakers Includes
Summary dry contacts for remote monitoring and alarm notification Transfer design
Fast-transfer design suitable for emergency lighting applications Listing
UL listed for emergency lighting service
Condition
Furnished as new equipment

CLIN 0003

Basis of Design: Myers 6-IE-6-BD2005-M
Characteristic
Requirement
Capacity
Approximately 6,000 VA/W
Input
277 VAC, single-phase, 60 Hz
Output
277 VAC, single-phase, 60 Hz
Battery type
VRLA (Valve Regulated Lead Acid)
Output breakers
Five (5) 20A, single-pole output breakers
Includes
Internal maintenance bypass
Transfer design
Standard-transfer design suitable for emergency lighting applications Listing
UL listed for emergency lighting service
Condition
Furnished as new equipment