USP Canaan Performance Work Statement Emergency Lighting Inverters
Updated
A Word document (41 KB) attached to USP Canaan IPS Supply and Startup, from the Federal Prison System / Bureau of Prisons. Due Nov 20, 2026, 4:00 PM (UTC-5).
File name: USP_Canaan_PWS_Emergency_Lighting_Inverters.docx
The full file is for paid members, or buy this bid alone.
Preview
Performance Work Statement (PWS)Emergency Lighting Inverter Systems Supply and Factory Startup ServicesUSP Canaan
1. Objective
The Federal Bureau of Prisons (BOP), USP Canaan, requires the procurement of replacement emergency lighting inverter systems and associated factory-authorized startup services. The Contractor shall furnish, deliver, and provide startup and commissioning services for the specified equipment. Installation of the equipment will be performed by the government and is not part of this requirement.
2. Scope
The Contractor shall provide emergency lighting inverter systems, associated batteries, integral breakers and monitoring components, manufacturer documentation, factory-authorized startup and commissioning services, operator familiarization training, and warranty support. The Contractor shall not provide equipment removal, demolition, electrical installation, conduit installation, circuit modifications, wiring connections, construction services, or disposal of existing equipment.
3. Supplies Required
The Government requires the contractor to furnish emergency lighting inverter systems and provide factory-authorized startup and commissioning services. Installation of the equipment will be performed by the Government or others and is not included in this requirement. Contract Line Item Numbers (CLINs)
CLIN
Description
Qty
Unit
0001
Emergency Lighting Inverter System, Brand Name or Equal to Myers Model 2-D-4-S-BD2005-ND2005-S EA
0002
Emergency Lighting Inverter System, Brand Name or Equal to Myers Model 2-D-1-S-BD2002-ND2002-S EA
0003
Emergency Lighting Inverter System, Brand Name or Equal to Myers Model 6-IE-6-BD2005-M EA
0004
Factory-Authorized Startup, Testing, Commissioning, and Operator Familiarization Training for CLINs 0001 through 0003 Lot
CLIN 0001 Salient Characteristics
The inverter system shall:
Provide approximately 10,000 VA/W capacity.
Accept 277/480 VAC, three-phase, 60 Hz, four-wire plus ground input. Provide 277/480 VAC, three-phase, 60 Hz, four-wire plus ground output. Include minimum 90-minute battery runtime.
Utilize VRLA battery technology.
Include five normally-on 20A single-pole output breakers. Include five normally-off 20A single-pole output breakers. Include summary dry contacts for remote monitoring.
Utilize fast-transfer technology.
Include a two-cabinet configuration.
Be UL listed for emergency lighting applications.
Be furnished as new equipment.
CLIN 0002 Salient Characteristics
The beginning of the document. Download the full file to read on.