5" REINFORCED CONCRETE PER DETAIL B8/C-501.
1"
KEYED NOTES
REMOVE EXISTING FILTER SAND.
2.
REMOVE EXISTING COARSE AGGREGATE.
3.
REFER TO SECTION A-A FOR REPLACEMENT MATERIALS.
4.
REMOVE EXISTING 4" HDPE AT LOW POINT DISCHARGE
AND INCREASE OPENING FOR PROPOSED 6" LINE. WALL
PENETRATION SHALL BE MADE WATER TIGHT WITH
METHOD AND PRODUCT TO BE ACCEPTED BY THE COR.
5.
CONSTRUCT CLEANOUT. SEE DETAIL F5/C-503.
6.
CONSTRUCT AREA DRAIN. SEE DETAIL F6 ON THIS SHEET.
7.
CLEAN AND SEAL PRECAST WALL CAP FOR ENTIRE LENGTH
OF WALL USING RADONSEAL OR COR APPROVED EQUAL
PRODUCT. REMOVE MATERIAL BETWEEN CAP JOINTS,
CLEAN OUT VOIDS, AND PLACE NEW BACKER ROD AND OR
SEALANT MATERIALS WHERE VOIDS MAY INTRODUCE
WATER. JOINT SEALANT TO BE APPROVED BY COR PRIOR
TO APPLICATION. ANY USE OF MASKING TAPE ON CAPS
MUST BE REMOVED SAME DAY IT IS APPLIED.
5"
1.
A
6" COMPACTED TYPE 'A' BASE
PER SPECIFICATION 31 20 11.
COMPACTED SUBGRADE PER
SPECIFICATION 31 20 11.
END CAP (TYP.)
4'-1/2" MAX.
EXISTING CONCRETE WALL
* SEE OVER EXCAVATION
NOTE THIS SHEET
NON-WOVEN GEOTEXTILE
FILTER FABRIC
4" PERFORATED HDPE
DRAINAGE PIPE. (TYP)
B
OVER EXCAVATION NOTES:
DISCHARGE TO OUTSIDE
FINISHED GRADE
DRAINAGE FILL
PER SPECS
6" SOLID HDPE
DRAINAGE PIPE.
SOILS BELOW CONCRETE REPAIR AREAS SHALL BE REMOVED TO A
DEPTH OF AT LEAST 30". SOILS BELOW 30" SHALL BE EVALUATED BY
A GEOTECHNICAL ENGINEER PRIOR TO PLACEMENT OF ANY FILL.
EVALUATION OF THE SOIL SUITABILITY WILL BE AT THE DISCRETION
OF THE GEOTECHNICAL ENGINEER. THE EVALUATION MAY BE
ACCOMPANIED BY T-PROBE TESTING, DYNAMIC CONE
PENETROMETER (DCP) TESTING, OR ANY OTHER METHODS DEEMED
NECESSARY BY THE GEOTECHNICAL ENGINEER. ANY FILL PLACED
SHALL MEET REQUIREMENTS OF LOW VOLUME CHANGE (LVC)
MATERIAL AS DEFINED BY SPECIFICATION 31 20 11.
1'-6"
16.9'
A
A
END CAP (TYP.)
B
NON-WOVEN GEOTEXTILE
FILTER FABRIC
12.6'
6" SOLID HDPE
DRAINAGE PIPE
6" SOLID HDPE
DRAINAGE PIPE.
C
A
4" PERFORATED
HDPE DRAINAGE PIPE
13.9'
C7
4" PERFORATED HDPE
DRAINAGE PIPE. (TYP)
UNDISTURBED
EXISTING SUBGRADE
C
SECTION A-A
SCALE: N.T.S.
9.4'
EXISTING WALL
3'-6"
6" SOLID HDPE
DRAINAGE PIPE.
FINISHED GRADE
SEE GRADING PLANS
24" INTEGRATED DUCTILE IRON FRAME
AND GRATE TO MATCH BASIN O.D.
EXISTING JUNCTION BOX
D
D
12" THICK LAYER OF DRAINAGE FILL
WRAP AROUND PERFORATIONS PER
SPEC 31 20 11.
NYLOPLAST DRAIN BASIN
EXISTING
FILTER SAND
RISER SHALL BE 24" DIA. OR 6" GREATER IN
DIA. THAN THE LARGEST CONNECTED PIPE.
NON-WOVEN GEOTEXTILE
FILTER FABRIC WRAP
AROUND PERFORATIONS AND
OUTSIDE OF DRAINAGE FILL.
CONTRACTOR SHALL HAND DRILL 34" DIAMETER
The beginning of the document. Download the full file to read on.
Other documents in this bid
- Bid document
- Attachment 11: Fort Sill NC Plan Set Reduced 9 of 11
- Attachment 12: Fort Sill NC Plan Set Reduced 10 of 11
- Attachment 1: Fort Sill NC Invitation for Bids Statement of Work
- Attachment 2: Fort Sill NC Combined Specifications
- Attachment 3: Fort Sill NC Plan Set Reduced 1 of 11
- Attachment 6: Fort Sill NC Plan Set Reduced 4 of 11
- Attachment 7: Fort Sill NC Plan Set Reduced 5 of 11
- Attachment 9: Fort Sill NC Plan Set Reduced 7 of 11
- Prebid Request for Information Fort Sill Gravesite Expansion and FCA
- Bid document
- Fort Sill NC Plan Set Reduced Amendment 1 of 11