Specifications
Updated
A PDF document (5.9 MB) attached to Building SH50 Replace Water Source Heat Pump, from the Department of the Navy. Due Nov 19, 2026, 3:00 PM (UTC-5).
File name: N4008525B0082 Specs.pdf
The full file is for paid members, or buy this bid alone.
Preview
25-0082
REPLACE SPLIT SYSTEM, BLDG HP259
CONTRACT N40085-25-B-0082
NAVFAC SPECIFICATION
NO. 25-0082
REPLACE SPLIT SYSTEM, BLDG HP259
AT THE
MARINE CORPS BASE, CAMP LEJEUNE, NORTH CAROLINA
DESIGN BY:
Nicholas J. Vella, PE
Design Branch, Mechanical Section
SPECIFICATION PREPARED BY:
Kim R. Sample
Date: October 26,2026
SPECIFICATION APPROVED BY:
Digitally signed by
MAAS.CHRISTOPHER.JETT.1588040727
DN:
MAAS.CHRISTOPHER.JETT.1588040727 CN=MAAS.CHRISTOPHER.JETT.1588040727, OU=USMC, OU=PKI, OU=DoD, O=U.S.
Government, C=US
Date: 2026.10.26 14:54:14-04'00'
Christopher J. Maas, P.E.
Director Design Branch, Public Works Division
Jonathan D. McGuire, Commander, CEC, U.S. Navy for
Commander, Naval Facilities Engineering
25-0082
SECTION COVER
PROJECT: 25-0082
TITLE: BUILDING BUILDING HP259 MECHANICAL REPLACEMENT
25-0082.PDF (CONTRACT DRAWINGS SHEETS G001 THROUGH E103)
PUBLISH.PDF (SPECS)
REGISTER.PDF (SUBMITTAL REGISTER)
25-0082 PROJECT SUMMARY.PDF (THIS DOCUMENT)
SCOPE OF WORK:
THE CONTRACTOR SHALL PROVIDE ALL MATERIAL, LABOR, EQUIPMENT, AND
SUPERVISION REQUIRED TO ACCOMPLISH THE FOLLOWING:
COMPLETE MECHANICAL REPLACEMENT OF THE HVAC SYSTEMS SERVING BUILDING
HP259, INCLUDING THE INSTALLATION OF A NEW 20-TON SPLIT SYSTEM AIR HANDLING
UNIT (AHU-1) AND MATCHING OUTDOOR AIR-COOLED CONDENSING UNIT (CU-1),
DUCTWORK CONNECTIONS, CONDENSATE DRAIN LINES, REFRIGERANT PIPING, AND
ASSOCIATED ELECTRICAL AND CONTROL SYSTEMS.
GENERAL DESCRIPTION
REPLACE THE EXISTING SPLIT SYSTEM AIR HANDLING UNIT (AHU-1) AND MATCHING
OUTDOOR CONDENSING UNIT (CU-1) WITH A NEW 20-TON SYSTEM FEATURING AN ECM
FAN MOTOR, COMPATIBLE WITH R-454B OR R-32 REFRIGERANT. TIE THE NEW SPLIT
SYSTEM INTO EXISTING DUCTWORK AND ELECTRICAL SYSTEMS. DEMOLISH AND
REPLACE SPECIFIED REFRIGERANT LINES, CONDENSATE LINES, AND ASSOCIATED
CONTROLS. PROVIDE NEW ELECTRICAL CONNECTIONS, FOR THE AHU-1 AND A NEW
DISCONNECT FOR CU-1 IN EXISTING DISCONNECT LOCATIONS, COMPLETELY REPLACING
OLD CIRCUITS, BREAKERS, AND CONDUIT.
IMPACT STATEMENT:
DUE TO THE DEMOLITION AND INSTALLATION OF THE MAIN 20-TON AIR HANDLER AND
ASSOCIATED CONDENSING UNIT, WORK WITHIN THE BUILDING (EXCLUDING THE
MECHANICAL ROOM) MUST BE PERFORMED STRICTLY OUTSIDE OF STANDARD
OPERATING HOURS (WEEKDAYS 0800–1630) TO MINIMIZE DISRUPTION TO ONGOING
OPERATIONS. ALL POWER OUTAGES MUST BE SCHEDULED ON WEEKENDS OR OUTSIDE
NORMAL WORKING HOURS, REQUIRING A MINIMUM OF FIVE (5) BUSINESS DAYS'
ADVANCED NOTICE TO THE CONTRACTING OFFICER. BUILDING CAN REMAIN OCCUPIED
AND FUNCTIONAL; ALL WORK WILL BE IN THE MECHANICAL ROOM AND IN OUTDOOR