Exhibit 3 PIP-II Low Conductivity Water LCW System Instrumentation Specification
Updated
A PDF document (194 KB) attached to Pip-Ii F-37 Building LWC Pump Room Piping System Installation, from the Department of Energy. Due Nov 19, 2026, 2:00 PM (UTC-6).
File name: EXHIBIT_3_ED0042584_PIP-II_Low_Conductivity_Water_LCW_System_Instrumentation_Specification.pdf
The full file is for paid members, or buy this bid alone.
Preview
PIP-II F37 Low Conductivity Water (LCW) System
Instrumentation Specification
Document number: ED0042584
Document Approval
Signatures Required
Originator: Mike Hanson, Sr Fluids Engineer
Reviewer: Matt Slabaugh, BLDGI L3 Manager
Approver: Jerry Leibfritz, Linac Installation & Commissioning L2 Manager
Date Approved
PIP-II Template
Revision History
Revision
A
Date of Release
May 2025
January 2026
Fermi National Accelerator Laboratory
Description of Change
Initial Release for Review
Issue for Bid
PIP-II Template
1.
2.
3.
4.
5.
6.
Fermi National Accelerator Laboratory
PIP-II Template
1. Purpose
This document is part of the Proton Improvement Plan-II (PIP-II) Building Infrastructure procurement package for the Low Conductivity Water (LCW) System. It contains a detailed description of the instrumentation and process filters that will be procured and installed in the F37 Pump Room portion of the PIP-II LCW System. This document can be found in Teamcenter under #ED0042585.
2. Reference Documents
#
Reference
P&ID’s (for reference only)
2D installation drawings
Document #
F10151066
SH01/SH02
F10170043
3. Equipment Specification for Linac Gallery
Item
Differential Pressure
Switch
Differential Pressure
Gage
Flow Transmitter
Flow Transmitter
Flow Transmitter
Fermi National Accelerator Laboratory
Requirement Statement
• Ashcroft B Series
• Pipe Size: ¼” FNPT
• Epoxy coated aluminum enclosure
• 30IW - 10 psi setpoint
• Part Number: Ashcroft Model 45-1127-SD-02-L-XSG-15#
• 4-1/2” Dial
• 316SS Process Connection
• ¼” Male NPT
• 0-15 psig gage
• ROSEMOUNT 8800 REDUCER VORTEX FLOW METER, 2 INCH
(DN50)
• Part Number 8800DR020SA1N1D1M5
• ROSEMOUNT 8800 REDUCER VORTEX FLOW METER, 6 INCH
(DN150)
• Part Number 8800DR060SA1N1D1M5
• ROSEMOUNT 8705 FLANGED MAGNETIC FLOW METER
SENSOR, 6 INCH (DN150)
• Part Number 8705TSA060C1M0
• ROSEMOUNT 8732E MAGNETIC FLOW METER TRANSMITTER
• Part Number 8732EMR1A1M4
Quantity
PIP-II Template
Dissolved Oxygen
Sensor
Temperature
Transmitter
Particulate Filter - F1
Particulate Filter – F2
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Particulate Filter – F3
•
Level Transmitter
Conductivity Meter
Pressure Transmitter
Pressure Gage
Fermi National Accelerator Laboratory
Metler Toledo #58037407
5-1000 ml/min sample rate
0-10,000 ppb range
Kodiak Controls Sure Site
Type BA connection
Plastic Flag Material
Stainless Housing and Float Material
The beginning of the document. Download the full file to read on.
Other documents in this bid
- Bid document
- Exhibit 10 ESH Requirements
- Exhibit 11 Submittals
- Exhibit 12 Quality Requirements
- Exhibit 13 CESHC
- Exhibit 16 2025 Construction Insurance Requirements
- Exhibit 18 Injury Illness Questionaire
- Exhibit 19 General Decision Number 05 18 2026
- Exhibit 20 SF1413-23a
- Exhibit 21 Bid Bond
- Exhibit 22 Payment Bond
- Exhibit 23 Performance Bond