Home / Pip-Ii F-37 Building LWC Pump Room Piping System… / Document

Exhibit 3 PIP-II Low Conductivity Water LCW System Instrumentation Specification

Updated

A PDF document (194 KB) attached to Pip-Ii F-37 Building LWC Pump Room Piping System Installation, from the Department of Energy. Due Nov 19, 2026, 2:00 PM (UTC-6).

File name: EXHIBIT_3_ED0042584_PIP-II_Low_Conductivity_Water_LCW_System_Instrumentation_Specification.pdf

Download the full documentSee the bid

The full file is for paid members, or buy this bid alone.

Preview

PIP-II F37 Low Conductivity Water (LCW) System
Instrumentation Specification
Document number: ED0042584
Document Approval
Signatures Required
Originator: Mike Hanson, Sr Fluids Engineer
Reviewer: Matt Slabaugh, BLDGI L3 Manager
Approver: Jerry Leibfritz, Linac Installation & Commissioning L2 Manager

Date Approved

PIP-II Template

Revision History
Revision
A

Date of Release
May 2025
January 2026

Fermi National Accelerator Laboratory

Description of Change
Initial Release for Review
Issue for Bid

PIP-II Template

1.

2.

3.

4.

5.

6.

Fermi National Accelerator Laboratory

PIP-II Template

1. Purpose

This document is part of the Proton Improvement Plan-II (PIP-II) Building Infrastructure procurement package for the Low Conductivity Water (LCW) System. It contains a detailed description of the instrumentation and process filters that will be procured and installed in the F37 Pump Room portion of the PIP-II LCW System. This document can be found in Teamcenter under #ED0042585.

2. Reference Documents

#

Reference

P&ID’s (for reference only)

2D installation drawings

Document #
F10151066

SH01/SH02

F10170043

3. Equipment Specification for Linac Gallery

Item
Differential Pressure
Switch

Differential Pressure
Gage

Flow Transmitter
Flow Transmitter
Flow Transmitter

Fermi National Accelerator Laboratory

Requirement Statement
• Ashcroft B Series
• Pipe Size: ¼” FNPT
• Epoxy coated aluminum enclosure
• 30IW - 10 psi setpoint
• Part Number: Ashcroft Model 45-1127-SD-02-L-XSG-15#
• 4-1/2” Dial
• 316SS Process Connection
• ¼” Male NPT
• 0-15 psig gage

• ROSEMOUNT 8800 REDUCER VORTEX FLOW METER, 2 INCH

(DN50)
• Part Number 8800DR020SA1N1D1M5

• ROSEMOUNT 8800 REDUCER VORTEX FLOW METER, 6 INCH

(DN150)
• Part Number 8800DR060SA1N1D1M5

• ROSEMOUNT 8705 FLANGED MAGNETIC FLOW METER

SENSOR, 6 INCH (DN150)

• Part Number 8705TSA060C1M0

• ROSEMOUNT 8732E MAGNETIC FLOW METER TRANSMITTER

• Part Number 8732EMR1A1M4

Quantity

PIP-II Template

Dissolved Oxygen
Sensor

Temperature
Transmitter
Particulate Filter - F1
Particulate Filter – F2

•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•

Particulate Filter – F3

•

Level Transmitter

Conductivity Meter

Pressure Transmitter
Pressure Gage

Fermi National Accelerator Laboratory

Metler Toledo #58037407
5-1000 ml/min sample rate
0-10,000 ppb range
Kodiak Controls Sure Site
Type BA connection
Plastic Flag Material
Stainless Housing and Float Material

The beginning of the document. Download the full file to read on.