1.The Q&A # 40 refers to attachment #1 for Corner guards. We did not find any green dots in the attachment A for corner guards. VA Answer: Refer to Attachment 1 – attached.
2. Q#23 & #54 contradict each other.
Are we to follow Level 2 containment or not?
VA Answer: Yes, contractor to follow Level II Infection Prevention and Control Precaution. 3.Q#69,#72,#74,#91& #14 contradict each other.
Please confirm the super can be dual hatted and you don’t need 3 personals on site. VA Answer: The superintendent may be dual-hatted; that is, they may also serve as the Safety or QC representative, but not as the project manager or as both the Safety and QC representatives. 4. Q&A#80- answer- COR will provide Specification Section 10 26 00 as an amendment. We have not received it till now. When will this be issued? VA Answer: Yes, it will be issued.
5. Q&A #5 - Where should personal items and furniture be stored during each phase of construction? VA - VA will relocate personal items; the contractor shall find a location outside the VA for storing furniture at their own expense. When re-installing furniture, the VA will let the contractor know if a room is getting new furniture. If new furniture is installed, the VA will install. If VA supplies furniture, we are responsible for disposal of furniture, this is unknown at this time. VA Answer: Correct, the contractor will be responsible for disposal of furniture if the VA installs new furniture.