LIGHTING FIXTURE SCHEDULE

TYPE

FA

BOD

MANUFACTURER

LITHONIA

Panelboard: PANEL A

MODEL NUMBER

DESCRIPTION

CLX-L48-4000LM-SEF-FDL-WD-MVOLT-GZ10-35K-80CRI-WH

LAMP/CCT/CRI

48' LED Linear w/ Standard efficiency. Flat diffuse lens. Wide distribution. White finish. Provide accessories required for suspended installation. Coordinate final suspension height and location with all trades. BAA and BABA Compliant.

A

DELIVERED

LUMENS

CONTROL

LED/3500K/80

0-10V 10%

4,236

WATTS

25.5

Ckt
A-1
A-3
A-5
A-7
A-9
A-11
A-13
A-15
A-17
A-19
A-21
A-23
A-25
A-27
A-29
A-31
A-33
A-35
A-37
A-39
A-41

ER1

EX BRANCH

CIRCUITS TO REMAIN

20A-3P

J A/C UNIT

20A-2P
EX

J HAND DRYER MENS

30A-3P
EX

J AIR COMPRESSOR

30A-2P
EX

J VEHICLE LIFT

ER PANEL B

400A, 240/120V, 3PH, 4W

60A-3P
EX

J CONDENSING UNIT

20A-2P

ER2

ER1

B

J

TYPICAL ALL BRANCH

CIRCUITS

J HEAT PUMP

20A-2P
J

EX

Description

MAINT. LIGHT

MAINT LIGHT

MAINT LIGHT

BREAK ROOM LIGHT

BATH LIGHT

BAY 2 LIGHT

STOCK/POL LIGHT

OUTSIDE LIGHT

OUTSIDE LIGHT

OUTSIDE LIGHT

GENERAL LIGHT

EXISTING LOAD

Trip (A) Poles FN/Note
E
E
E
E
E
E
E
E
E
E
E
E

VEHICLE LIFT

E

GARAGE DOOR

GARAGE DOOR

OUTSIDE BREAK LIGHTS

GARAGE DOOR

GARAGE DOOR

E
E
E
E
e

HAND DRYER MENS

E

Phase A
Load (VA)

Load Classification
Other
Receptacle - General

Phase B
Load (VA)

Phase C
Load (VA)

FN/Note Poles Trip (A)
E
E

HAND DRYER WOMANS

E

WELDING EQUIPMENT

E

HEAT PUMP

EX

J WELDING EQUIPMENT

E

CONDENSING UNIT

E

Spare

E

AIR COMPRESSOR

E

UNIT HEATER

E

A/C UNIT

9 kVA

82 A

Connected
17360 VA
1080 VA

9 kVA

82 A

1 kVA

9A

ELECTRICAL POWER OUTAGES, IF REQUIRED, SHOULD BE STRATEGICALLY

MINIMIZED AND SCHEDULED CLOSELY WITH OWNER. CHANGEOVERS COULD BE

REQUIRED TO OCCUR AT ANY HOUR.

2.

MAINTAIN ALL SERVICE CLEARANCES REQUIRED BY THE NEC.

3.

INSTALL ALL CONDUCTORS AS PER MANUFACTURER'S RECOMMENDATIONS.

4.

EXTERNAL MOUNTED SURGE PROTECTION DEVICES SHALL BE INSTALLED PER

MANUFACTURER'S GUIDELINES.

Factor
100.00%
100.00%

J

Demand
17360 VA
1080 VA

ELECTRICAL RISER KEYED NOTES

ER1

REFER TO PANEL SCHEDULE FOR ADDITIONAL PANEL AND CIRCUIT

DETAILS.

ER2

PULL BACK CIRCUIT TO NEAREST JUNCTION BOX. PROVIDE NEW AS

NECESSARY. PREPARE TO EXTEND TO NEW PANELBOARD.

ER3

SPLICE AND EXTEND CONDUCTORS FROM EXISTING BRANCH CIRCUITS TO

NEW PANEL. REFER TO SCHEDULES FOR PANEL A AND PANEL B FOR

ADDITIONAL BRANCH CIRCUIT INFORMATION.

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

COPPER CONDUCTOR

AND CONDUIT SIZING CHART

Panel Totals
Connected Load: 18 kVA
Connected Current: 51 A