ELECTRICAL GENERAL NOTES

LIGHTING CONTROL - SEQUENCE OF OPERATION

TAG

ACTIVATION

A

DECRIPTION

MANUAL ON/OFF

1.

NOT USED.

2.

SURFACE RACEWAY SHALL NOT BE USED IN ANY FINISHED AREAS WITHOUT

PRIOR APPROVAL OF THE DESIGN TEAM.

SCHEDULE

MANUAL LINE VOLTAGE TOGGLE SWITCH

N/A
3.

A

INSTALL DEVICES SUCH THAT NO TWO DEVICES ON OPPOSITES SIDES OF THE

SAME WALL ARE WITHIN 6" OF EACH OTHER.

4.

COORDINATE ALL DEVICES WITH ARCHITECTURAL PLANS AND CASEWORK.

5.

ALL LIGHTING FIXTURES SHALL BE INSTALLED IN SUCH A WAY THAT DRIVERS ARE

ACCESSIBLE WITHOUT CUTTING OF CEILING. THE DESIGN TEAM SHALL BE

NOTIFIED IMMEDIATELY OF AREAS WHERE THIS IS NOT POSSIBLE.

6.

ALL WALL-MOUNTED FIXTURES SHALL HAVE THEIR EXACT ROUGH-IN LOCATION

DETERMINED BY THE DESIGN TEAM PRIOR TO ROUGH-IN.

7.

UNLESS NOTED OTHERWISE BY DESIGNATED LIGHTING CONTROL ZONES, SWITCHES SHOWN SHALL CONTROL ALL FIXTURES IN THE ROOM.

8.

REFER TO ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS FOR

THE SPECIFIC DEVICE ROUGH-IN AND PLACEMENT. ANY DEVIATIONS FROM THE

ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS SHALL BE

REVIEWED AND APPROVED BY THE DESIGN TEAM PRIOR TO ROUGH-IN.

9.

ALL DEVICES, EQUIPMENT, FIXTURES, AND THE LIKE MUST BE GROUNDED BY USE

OF A PROPERLY SIZED GROUNDING CONDUCTOR. MECHANICAL AND

ELECTRICAL BONDS OF THE METALLIC RACEWAY SYSTEM SHALL BE MAINTAINED. GROUND AND BOND PER NEC ARTICLE 250.

A

10. ALL DISCONNECTS ON MECHANICAL EQUIPMENT SHALL BE MOUNTED ON

STRUCTURE TO ALLOW REMOVAL OF THE EQUIPMENT FOR MAINTENANCE WITH

A MINIMUM OF WIRING WORK. VERIFY NEC CLEARANCE REQUIREMENTS ARE MET

PRIOR TO ROUGH-IN.

B

B
CU-1

PANEL B-85,87

EX

EX

A
E3

L5-30R RECEPT

120V-1P/30A
E4

PANEL B-91

PANEL B-95

J

FA

EX

EX

EX

EXISTING PESTICIDE

STORAGE

EX

EX

TE

ELECTRICAL PLAN KEYED NOTES

EXISTING PARTS & TOOLS

EX

EXISTING FLAMABLE

STORAGE

EX

EXISTING FLAMABLE

STORAGE

C

14. INSTALL DEVICES SUCH THAT NO TWO DEVICES ON OPPOSITE SIDES OF THE

SAME WALL ARE WITHIN 24" OF EACH OTHER.

E7

EXISTING PESTICIDE

STORAGE

EXISTING PARTS & TOOLS

EX

E2
12"

EX

12. SURFACE RACEWAY SHALL NOT BE USED IN ANY FINISHED AREAS WITH PRIOR

APPROVAL FROM THE DESIGN TEAM.
13. ALL RECEPTACLE CIRCUITS SHALL HAVE DEDICATED NEUTRAL.

48"
12"

EX

AS-SCP-1

E9 PANEL B-89

TE

L5-30R RECEPT

120V-1P/30A

PANEL B-93

J

L5-30R L5-30R

WP

EX

11. MAINTAIN SERVICE CLEARANCE AROUND MECHANICAL & ELECTRICAL

EQUIPMENT. DO NOT ROUTE PIPING OR CONDUIT IN CLEARANCE SPACE.

EX
E7

EX

EX

GFI

EX

E7

MAINTENANCE YARD

MAINTENANCE YARD

EX

E2

PROVIDE (2) L5-30R RECEPTACLES FOR TELECOM USE. REFER TO

TECHNOLOGY DRAWINGS FOR ADDITIONAL DETAILS. COORDINATE WITH