Tinker AFB, OK
TAFB Technical Specifications 2019
SECTION 23 03 00
BASIC MECHANICAL MATERIALS AND METHODS
PART 1
1.1
GENERAL
REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only. Unless specifically noted, the current edition of the reference shall be used.
ASTM INTERNATIONAL (ASTM)
ASTM B117
Standard Practice for Operating Salt Spray
(Fog) Apparatus
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE C2
National Electrical Safety Code
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA MG 1
Motors and Generators
NEMA MG 10
Energy Management Guide for Selection and Use
of Fixed Frequency Medium AC Squirrel-Cage
Polyphase Induction Motors
NEMA MG 11
Energy Management Guide for Selection and Use
of Single Phase Motors
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70
1.2
National Electrical Code
SUBMITTALS
Government approval is required for all submittals. The following shall be submitted in accordance with Section 01 33 00 SUBMITTAL PROCEDURES: SD-03 Product Data
Certification
1.3
RELATED REQUIREMENTS
This section applies to all sections of Divisions: 21, FIRE SUPPRESSION; 22,
PLUMBING; and 23, HEATING, VENTILATING, AND AIR CONDITIONING of this
project specification, unless specified otherwise in the individual section.
April 2019
Section 23 03 00
Tinker AFB, OK
1.4
TAFB Technical Specifications 2019
QUALITY ASSURANCE
1.4.1
Material and Equipment Qualifications
Provide materials and equipment that are standard products of manufacturers regularly engaged in the manufacture of such products, which are of a similar material, design and workmanship. Standard products shall have been in satisfactory commercial or industrial use for 2 years prior to bid opening. The 2-year use shall include applications of equipment and materials under similar circumstances and of similar size. The product shall have been for sale on the commercial market through advertisements, manufacturers' catalogs, or brochures during the 2 year period. 1.4.2
Alternative Qualifications
Products having less than a two-year field service record will be acceptable if a certified record of satisfactory field operation for not less than 6000 hours, exclusive of the manufacturer's factory or laboratory tests, can be shown.
1.4.3
Service Support
The equipment items shall be supported by service organizations. Submit a certified list of qualified permanent service organizations for support of