single / dual duct terminals

ELECTRIC COILS

To make a coil selection:
1. Check the desired kW is available in desired unit size and number of stages. (Required to prevent excessive watt density and current draw, while taking into account unit size limitations.) 2. Check the desired minimum airflow limit is within recommended operating range. (Ensures velocity pressure will be sufficient to close airflow sensing switch.)
3. Multiply desired minimum airflow limit by a factor of 0.0142 and check the result is equal to or greater than desired kW. (Limits temperature rise across the coil to 45°F.)
kW ≤ cfm x 0.0142
These requirements established to prevent excessive temperature rise caused by low airflow and/or oversized coils. Minimum airflow limits

Titus electric heating coils are specifically designed for use with VAV terminal units. They include an extended plenum section and diffuser plate to minimize stratification. The heating elements are designed to minimize hot spots and nuisance tripping of the thermal cutouts. Must be within recommended ranges to ensure proper operation and long service life. For optimum diffuser performance and maximum thermal comfort, coil discharge temperatures should not be more than 15°F above desired room temperatures. For proper coil operation it is recommended that coil discharge temperatures do not to exceed 100°F. Note: The Titus 480V, 3-phase electric
heat configuration is 4-wire wye. 3-wire
configuration is available.

PESV, AESV, DESV / APPLICATION DATA (STAGED HEAT)

Inlet Size

Heating cfm
Range
55-225

85-350

105-500

135-650

190-900

225-1050

300-1400

425-2000

575-3000

750-4000

24x16

1800-8000

Useful formulas: kW =

cfm x ΔT
3160

Where ΔT = air temperature rise.

120V 1 Phase
kW Range

208V 1 Phase
kW Range

240V 1 Phase
kW Range

277V 1 Phase
kW Range

208V 3 Phase
kW Range

480V 3 Phase
kW Range

Min
0.5
1.0
1.5
0.5
1.0
1.5
0.5
1.0
1.5
0.5
1.0
1.5
0.5
1.0
1.5
0.5
1.0
1.5
0.5
1.0
1.5
0.5
1.0
1.5
0.5
1.0
1.5
0.5
1.0
1.5
1.0
2.0
3.0

Min
0.5
1.0
1.5
0.5
1.0
1.5
0.5
1.0
1.5
0.5
1.0
1.5
0.5
1.0
1.5
0.5
1.0
1.5
0.5
1.0
1.5
0.5
1.0
1.5
1.0
2.0
3.0
1.0
2.0
3.0
1.0
2.0
3.0

Min
1.0
1.5
2.0
1.0
1.5
2.0
1.0
1.5
2.0
1.0
1.5
2.0
1.0
1.5
2.0
1.0
1.5
2.0
1.0
1.5
2.0
1.0