single / dual duct terminals
Redefine your comfort zone. ™ | www.titus-hvac.com
PERFORMANCE DATA
RECOMMENDED PRIMARY AIR CFM RANGES / ALL TERMINALS
Control Types:
PESV / Pneumatic
AESV / Analog Electronic
DESV / Digital Electronic
QUICK SELECTION PROCEDURE
1. Select unit inlet size based upon acoustic parameters and/ or maximum pressure drop requirements, using pages
M15-M16
2. Check inlet size selection against cfm control limits based on control type shown on this page
3. Select accessories (multi-outlets, attenuators) as required 4. Select reheat coil, if required. Make your selection using the actual heating flow rate, not cooling.
CFM Ranges of Minimum and Maximum Settings
M
Inlet Size
Total CFM
Range
24 X 16
0-225
0-350
0-500
0-650
0-900
0-1050
0-1400
0-2000
0-3000
0-4000
0-8000
PESV - Pneumatic
Titus II Controller
Minimum
50-210
70-300
80-345
120-515
160-700
205-900
250-1110
330-1460
525-2335
665-2970
1245-5555
Maximum
90-225
125-350
145-500
210-650
285-900
370-1050
455-1400
600-2000
955-3000
1215-4000
2270-8000
PESV - Pneumatic
Titus I Controller
Minimum
65-210
90-300
100-345
150-515
205-700
260-900
325-1110
425-1460
675-2335
860-2970
1605-5555
Maximum
90-225
125-350
145-500
210-650
285-900
370-1050
455-1400
600-2000
955-3000
1215-4000
2270-8000
AESV - Analog Electronic
TA1 Controller
Minimum
50-225
70-350
80-500
120-650
160-900
205-1050
250-1400
330-2000
525-3000
665-4000
1245-8000
Maximum
50-225
70-350
80-500
120-650
160-900
205-1050
250-1400
330-2000
525-3000
665-4000
1245-8000
DESV - Digital
Typical Controller
Minimum
30-225
40-350
45-500
70-650
90-900
120-1050
145-1400
190-2000
300-3000
385-4000
720-8000
Maximum
30-225
40-350
45-500
70-650
90-900
120-1050
145-1400
190-2000
300-3000
385-4000
720-8000
PERFORMANCE DATA
Note: On controls mounted by Titus but supplied by others (FMA or Factory Mounting Authorization), these values are guidelines only. Controls mounted on an FMA basis are calibrated in the field.
M16
single / dual duct terminals
PERFORMANCE DATA
Size
Min
ΔPs
1000
1000
1100
1200
1300
1200
1400
1600
1800
2000
1500
1800
2100
2400
2700
2000
2400
2800
3200
3600
3900
4600