Home / Facility Readiness and Maintenance Execution (FRAME)… / Document

Bid document

Updated

A PDF document (719 KB) attached to Facility Readiness and Maintenance Execution (FRAME) Request for Proposal (RFP) - DRAFT, from the Department of the Air Force. Due Jan 31, 2027, 4:30 PM (UTC-8).

File name: TL HPGSA-PV-229-VTE-01242024v2.pdf

Download the full documentSee the bid

The full file is for paid members, or buy this bid alone.

Preview

LOSC ISI Program
Exterior Pressure Vessel Inspection
Date
Inspector/Level
1/24/2024
Brett Strickland / II
Serial Number
750400-1V7

Report Number: CHI-PV-229-VTE-2024
Client
Call Henry Inc.

National Board Number
N/A

Manufacturer & Year Built
Taylor Forge

MAWP

6,000 PSI

Temp. Range
-25 to 140 °F

Commodity
Gaseous Nitrogen

Vessel ID
PV-229

Vessel Type
Horizontal Pressure Vessel

Exam Type
External

Location/Area

SLC-4/HPGSA

Bld. Number
N/A

Room Number
N/A

Required Equipment
Ladder, flashlight, mirror, bubble leak, picks, hammer, ruler, camera

Access Notes
The vessel was located at the High Pressure Gas Storage Area (HPGSA) on SLC-4. Access must be set up in advance with the facility operator, Space X.

Primary
Condition of Heads
Condition of Shell
Evidence of Leakage
Dents/Deformations
Insulation/CUI
Paint

Previous Inspection Documentation
VTE: 2023
GP-R-142002 (2010)
Vessel Inspection
Comments

A/R/F/O

No Comments
Acceptable
No Comments
Acceptable
Leak at top head nozzle flange
Other
No Comments
Acceptable
N/A
No Comments
Acceptable
Areas of minor corrosion, cracked/chipped

Welds
Head to Shell Welds
Longitudinal Weld(s)
Nozzle Welds
Support/Saddle Welds
Skirt/Band Welds
Additional Component Welds

A/R/F/O

Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable

Comments
No Comments
No Comments
No Comments
No Comments
No Comments
No Comments

Attachments
Bolts/Flanges
Grayloc Connection
Drain
Other

A/R/F/O

Rejectable
Acceptable
N/A
Other

Comments
Dissimilar metals, leak at top head nozzle flange
No Comments
No Comments
Moderate corrosion on isolation valve

LOSC ISI Program
Vessel Inspection Cont.
Supports

A/R/F/O

Skirts/Bands
Acceptable
Saddle/Steel Support Structure
Acceptable
Anchor Bolting
Acceptable
Pedestal/Grouting
Acceptable
Concrete Pad
N/A
Foundation
Other
Containment
Acceptable
Ladders/Stairs
N/A
Platforms
N/A
Grating
N/A
Handrails/Kickplates
N/A

No Comments
No Comments
No Comments
No Comments
No Comments
Offset/gap between foundations
No Comments
No Comments
No Comments
No Comments
No Comments

Auxiliary Equipment
Gauges
Sensors/Transducer
Sight Glass/Liquid Level
Relief Valve
Grounding
Other

Comments
Missing NCR sticker, @ 4,700 PSI
No Comments
No Comments

The beginning of the document. Download the full file to read on.

Other documents in this bid