VA Project No. 833CM3030
Correct FCA Deficiencies
Camp Nelson National Cemetery, KY
100% CD2
7-8-2025
SECTION 26 29 23
ENGINE CONTROL AND MONITORING
PART 1 – GENERAL
1.1
A.
B.
1.2
A.
B.
C.
D.
1.3
A.
B.
C.
D.
1.4
A.
B.
1.5
SUMMARY
This Section includes furnishing and installing a factoryassembled, UL-listed fuel dispensing system controller for use with protected fuel storage tanks..
Related Sections:
1.
Division 26 – Electrical connections.
2.
Section 23 11 13 – Fuel Storage Tanks.
3.
Section 26 32 13 – Engine Generators.
4.
Division 33 – Fuel Distribution (if applicable).
SREFERENCES
UL 508A – Industrial Control Panels.
NEC – National Electrical Code.
NFPA 30 – Flammable and Combustible Liquids Code.
NFPA 110 – Emergency and Standby Power Systems.
SUBMITTALS
Product Data: Controller functionality, wiring schematics, and connection requirements.
Shop Drawings: Panel layout, dimensions, and mounting details. Certifications: UL 508A listing and manufacturer qualifications. Warranty documentation.
QUALITY ASSURANCE
Manufacturer Qualifications: Minimum 5 years experience in fuel dispensing control systems.
Products shall be listed and labeled per UL standards.
DELIVERY, STORAGE, AND HANDLING
A.
Deliver controller in manufacturer’s original packaging with identification labels intact.
B.
Store indoors, protected from moisture and damage.
1.6
A.
WARRANTY
Provide manufacturer’s standard one-year warranty against defects in materials and workmanship.
PART 2 – PRODUCTS
ENGINE CONTROL AND MONITORING
SECTION 26 29 23 - 1
VA Project No. 833CM3030
Correct FCA Deficiencies
2.1
2.2
Camp Nelson National Cemetery, KY
100% CD2
7-8-2025
MANUFACTURER
A.
SafeSite, LLC – SafeSite DSC (Dispensing System Controller).
B.
Substitutions: Comply with Section 01 25 00 – Substitution Procedures.
CONTROLLER ASSEMBLY
A.
Type: Factory-assembled fuel dispensing system controller for outdoor use.
B.
Enclosure:
1. Type 4X, UL Listed, stainless steel.
2. Weather- and corrosion-resistant.
3. Lockable access door.
C.
Control Features:
1. Digital fuel dispenser control.
2. Emergency Stop (E-Stop) circuit.
3. Motor starter for fuel transfer pump.
4. Remote fill interface.
5. Dry contact integration for leak detection, tank level, and generator control panels.
6. Terminal blocks for field wiring.
7. System test switch.
D.
Electrical:
1. Voltage: 120V or 240V (confirm with system requirements). 2. Circuit Protection: Circuit breakers or fuses as required.
The beginning of the document. Download the full file to read on.
Other documents in this bid
- Jessamine Camp Nelson Building
- Jessamine Camp Nelson Heavy
- Jessamine Camp Nelson Highway
- From CNNC FCA Corrections CONS BD DRAWINGS VOL 1
- From CNNC FCA Corrections CONS BD DRAWINGS VOL 1
- From CNNC FCA Corrections CONS BD DRAWINGS VOL 1
- From CNNC FCA Corrections CONS BD DRAWINGS VOL 1
- From CNNC FCA Corrections CONS BD DRAWINGS VOL 1
- From CNNC FCA Corrections CONS BD DRAWINGS VOL 1
- From CNNC FCA Corrections CONS BD DRAWINGS VOL 1
- From CNNC FCA Corrections CONS BD DRAWINGS VOL 1
- From CNNC FCA Corrections CONS BD DRAWINGS VOL 1