VA Project No. 833CM3030
Correct FCA Deficiencies
Camp Nelson National Cemetery, KY
100% CD2
7-8-2025
SECTION 33 56 10
TEMPORARY FUEL STORAGE TANKS
PART 1 – GENERAL
1.1 SUMMARY
A. This section covers the requirements for temporary fuel storage tanks to be used during construction, including one (1) 250-gallon gasoline storage tank and one (1) 250-gallon diesel storage tank. B. The Contractor shall provide, install, maintain, and remove the temporary fuel storage tanks.
C. The Contractor shall provide initial fueling of the tanks; all subsequent fueling will be the responsibility of the Customer. D. The Contractor shall ensure proper maintenance and compliance with all safety and environmental regulations.
1.2 REFERENCES
A. NFPA 30 – Flammable and Combustible Liquids Code
B. NFPA 31 – Standard for the Installation of Oil-Burning Equipment C. NFPA 37 – Standard for the Installation and Use of Stationary Combustion Engines
D. UL 142 – Standard for Steel Aboveground Tanks for Flammable and Combustible Liquids
E. EPA 40 CFR Part 112 – Spill Prevention, Control, and Countermeasure (SPCC) Rule
F. OSHA 29 CFR 1926 – Safety and Health Regulations for Construction
1.3 SUBMITTALS
A. Product Data: Manufacturer’s specifications for fuel storage tanks. B. Installation Plan: Proposed location, foundation, anchoring method, and spill containment provisions.
C. Safety Plan: Procedures for handling, refueling, spill response, and fire protection.
D. Compliance Documentation: Evidence that tanks meet applicable regulatory requirements.
PART 2 – PRODUCTS
2.1
TEMPORARY FUEL STORAGE TANKS
A. Tanks shall be factory-fabricated, UL 142-certified, double-walled aboveground storage tanks.
TEMPORARY FUEL STORAGE TANKS
SECTION 33 56 10 - 1
VA Project No. 833CM3030
Correct FCA Deficiencies
Camp Nelson National Cemetery, KY
100% CD2
7-8-2025
B. Each tank shall have a minimum capacity of 250 gallons.
C. Tanks shall include:
1. Lockable fill ports and venting system.
2. Fuel level gauges.
3. Emergency venting per NFPA requirements.
4. Secondary containment to prevent spills and leaks.
D. Gasoline and diesel tanks shall be clearly labeled with appropriate signage and hazard identification per OSHA and NFPA standards.
2.2 ACCESSORIES
A. Spill containment berms or double-walled containment as required by EPA regulations.
B. Fire extinguishers rated for fuel fires placed within 10 feet of tanks.
C. Leak detection system with audible and visual alarms. D. Grounding and bonding equipment per NFPA 30 requirements.
The beginning of the document. Download the full file to read on.
Other documents in this bid
- Jessamine Camp Nelson Building
- Jessamine Camp Nelson Heavy
- Jessamine Camp Nelson Highway
- From CNNC FCA Corrections CONS BD DRAWINGS VOL 1
- From CNNC FCA Corrections CONS BD DRAWINGS VOL 1
- From CNNC FCA Corrections CONS BD DRAWINGS VOL 1
- From CNNC FCA Corrections CONS BD DRAWINGS VOL 1
- From CNNC FCA Corrections CONS BD DRAWINGS VOL 1
- From CNNC FCA Corrections CONS BD DRAWINGS VOL 1
- From CNNC FCA Corrections CONS BD DRAWINGS VOL 1
- From CNNC FCA Corrections CONS BD DRAWINGS VOL 1
- From CNNC FCA Corrections CONS BD DRAWINGS VOL 1