LEGEND
LEACH FIELD POINT REPAIR
EXISTING SANITARY SEWER LINE
6" GRAVITY DISTRIBUTION PIPING
EX. LEACH FIELD LATERAL
SOIL BORINGS
PERFORM PIPE CCTV INVESTIGATION
& SELECTED LATERAL DRAIN POINT
REPAIRS (SEE NOTE 5)
CU-201
SEPTIC DISTRIBUTION BOX,
02 EX.
APPROX. INV. DEPTH 934.10
SERVICE EXISTING 1000 GAL SEPTIC TANK,
03 INV. 934.16 (SEE NOTE 2)
B-1
6" SCH 40 PVC SANITARY SEWER PIPE,
PROFILE SMOOTHLY BETWEEN EXISTING
INVERTS (SEE NOTE 4)
DE-ENERGIZE, TEMPORARILY RELOCATE OR
EXCAVATE AROUND WHILE IN PLACE, AND
REINSTALL BURIED ELECTRICAL SERVICE IF
NECESSARY FOR POINT REPAIR.
A
A
KEYNOTES
S.S. FULL BODY SERVICE TAP, ROMAC
04 SHIELDED TRANSITION COUPLING
CO
G
BRACE POLE DURING EXCAVATION.
COORDINATE WITH UTILITY PROVIDER.
REINSTALL/RETURN PROPANE STORAGE
TANK TO SERVICE. PROVIDE ALL NECESSARY
FITTINGS, HARDWARE, & SPECIALS.
(SEE NOTE 7)
RECONNECT EXISTING 4" SANITARY
SERVICE FROM REST & WASH HOUSE
WITH NEW FITTINGS (SEE NOTE 3)
B
13 RESTROOM TRAILER, TEMPORARY
05 SEWER CLEANOUT CU-201
CU-102
4 " SCH 40 PVC WATER LINE TO TEMP.
3 " REDUCED PRESSURE BACKFLOW PREVENTER
IN HEATED ENCLOSURE (WATTS 009M3-QT &
14 WATTS BOX WB-1 OR APPROVED EQUALS)
B
(SEE NOTE 7)
NEW 500 GALLON FUEL STORAGE TANK.
09 (SEE SPEC SECTION 23 11 13)
12 (SEE NOTE 7 & 8)
NOTES
B-2
1.
ALL WORK ON SEPTIC SYSTEM SHALL BE A PERFORMED CERTIFIED ONSITE SEWAGE SYSTEM
INSTALLER, LICENSED IN THE STATE OF KENTUCKY.
2.
DEWATER AND CLEAN EXISTING SEPTIC TANK. DAMAGED OR BROKEN BAFFLES SHALL BE REMOVED AND REPLACEMENTS CUSTOM-FABRICATED FROM FIBER REINFORCED POLYMER (FRP) OR PVC. ALL SOLID AND LIQUID WASTE SHALL BE TRANSPORTED OFFSITE AND LEGALLY DISPOSED OF.
3.
PRIOR TO CONSTRUCTION, VERIFY LOCATION OF ALL EXISTING SANITARY CONNECTIONS TO SEPTIC TANK AND UTILITIES ADJACENT PIPE TO BE REPLACED. CONFIGURATION MAY VARY FROM THAT SHOWN, RECONNECT EXISTING UTILITIES AND RESTORE SERVICE AT NO ADDITIONAL COST TO THE GOVERNMENT.
4.
SANITARY PIPE DEPTH ESTIMATED AND SHOWN. LOCATE, UNCOVER, PROTECT, AND ACCOMODATE EXISTING UTILITIES DURING REPLACEMENT.
5.
SUBMIT VIDEO AND RECOMMENDED POINT REPAIR LOCATIONS FOR APPROVAL. BASIS OF BID SHALL BE 60 LF OF LATERAL DRAIN PIPE, AT 12 INDIVIDUAL EXCAVATIONS.
6.
AT COLLAPSED LATERAL DRAINS, RECOMMENCE CCTV INVESTIGATION AFTER REPAIR, AT NO
ADDITIONAL COST TO THE GOVERNMENT.
7.
INSTALL 3 4" BFP & ENCLOSURE ON 4" TEMPORARY CONCRETE PAD. BFP, ENCLOSURE & TEMPORARY PAD TO REMAIN FOR DURATION OF CONSTRUCTION. REMOVE BFP, DEMOLISH 4" CONCRETE PAD,
CUT AND CAP 3 4" WATER LINE AT SADDLE, AND REMOVE BURIED PVC SERVICE LINE AFTER
The beginning of the document. Download the full file to read on.
Other documents in this bid
- Jessamine Camp Nelson Building
- Jessamine Camp Nelson Heavy
- Jessamine Camp Nelson Highway
- From CNNC FCA Corrections CONS BD DRAWINGS VOL 1
- From CNNC FCA Corrections CONS BD DRAWINGS VOL 1
- From CNNC FCA Corrections CONS BD DRAWINGS VOL 1
- From CNNC FCA Corrections CONS BD DRAWINGS VOL 1
- From CNNC FCA Corrections CONS BD DRAWINGS VOL 1
- From CNNC FCA Corrections CONS BD DRAWINGS VOL 1
- From CNNC FCA Corrections CONS BD DRAWINGS VOL 1
- From CNNC FCA Corrections CONS BD DRAWINGS VOL 1
- From CNNC FCA Corrections CONS BD DRAWINGS VOL 1