KU FDR CRT #119

10.075kA

23.67 (X/R)

10.315kA

26 (X/R)

KU FDR CRT #136

11.69kA

20.67 (X/R)

12.014kA

22.6 (X/R)

50N
51N

Relay U136

50N
51N

1-1/C-500 kcmil
CU, 675', [Conduit]

1-1/C-500 kcmil
CU, 675', [Conduit]

Relay U119

Relay 1

Relay 6

G

Relay 7

1-1/C-4/0 AWG

CU, 170', [Conduit]

1-1/C-4/0 AWG

CU, 155', [Conduit]

To MCC3N

To Busduct A&B

To Panel MP5

kV
0.

4-1/C-500 kcmil
CU, 85', [Conduit]

1000 HP
Induction
16.7%

CT1

CHILL WTR PMP #1

AHU4-1

100 HP
Induction
16.7%

COOLING TWR #3

PNL PP

SQD LJ

600/400A

SQD JJ

250/225A

kV
0.

SQD JJ

250/225A

SQD HJ

150/150A

SQD HJ 60A Frame
60/20A

1-1/C-12 AWG

CU, 10', [Conduit]

SQD LJ

600/400A

SQD RK

2500/1600A

1-1/C-6 AWG

CU, 10', [Conduit]

SQD HJ 60A Frame
60/40A

Panels E1, E2 and T-E2 are located in
Chiller Plant and fed from Main Hospital.
See Main Hospital for one-line.

BASIN HTR #2

100 HP
Induction
16.7%

T-T1(PNL PP)

75 kVA

0.48 - 0.208 kV

4.35%

SQD QB

225/225A

SQD JJ

250/200A

1-1/C-8 AWG

10', [Conduit]
0CU,
.4
kV

1-1/C-4/0 AWG

CU, 65', [Conduit]

1-1/C-4/0 AWG

20', [Conduit]
0CU,
.4
kV

15 HP

Induction
16.7%

250 HP
Induction
16.7%

SQD JJ

250/200A

SQD HD

150/150A

kV

CT2

150 HP
Induction
16.7%

PNL LP

100 HP
Induction
16.7%

SQD JJ

250/225A

0.

100 HP
Induction
16.7%

SQD JJ

250/250A

1-1/C-1/0 AWG

CU, 50', [Conduit]

SQD LJ

600/400A

1-1/C-4/0 AWG

CU, 70', [Conduit]

0.

SQD JJ

250/225A

1-1/C-4/0 AWG

CU, 10', [Conduit]

SQD JJ

250/200A

SB HSB2

SB HSB1

1-1/C-3/0 AWG

CU, 75', [Conduit]

SQD JJ

250/200A

CHILLER #1B

kV

SQD RK

2500/1600A

kV

SQD NW16H3

1600/1600A

SQD NW32H3

3200/3200A

CHILLER #3

CHILLER #1A

T-2B
2000 kVA

12.47 - 0.48 kV

5.71%

SWB MAIN 2B

1-1/C-4/0 AWG

CU, 30', [Conduit]

kV

T-2A
2000 kVA

12.47 - 0.48 kV

5.71%

SQD NW32H3

OPEN

3200/2500A

SQD NW20H3

2000/2000A

0.

4-1/C-500 kcmil
CU, 60', [Conduit]

SQD NW32H3

3200/3200A

1100 HP
Induction
16.7%

1-1/C-4 AWG

CU, 50', [Conduit]

5-1/C-500 kcmil
CU, 90', [Conduit]

To MCC4N

SQD VR-15075-12

1200A

BRK T-2B

CHILLER #2

1-1/C-3/0 AWG

CU, 70', [Conduit]

1-1/C-8 AWG

10', [Conduit]
0CU,
.4
kV
kV

To Panel R1

SWB MAIN 2A

1-1/C-10 AWG

CU, 40', [Conduit]

.4
0.

Siemens RLX-800
800/400A

Siemens RLX-800
800/800A
1-1/C-350 kcmil
CU, 1', [Conduit]

To Panel R2

Siemens RLX-800
800/600A

800A-(Generic)
CU, 75'

To Busduct C&D

Siemens RLX-800
800/400A

2-1/C-600 kcmil
CU, 325', [Conduit]

To ESB 4 via
ATS Equip

Siemens RLX-800
800/350A

2-1/C-500 kcmil
CU, 340', [Conduit]

2-1/C-500 kcmil