Bowling Tower SWB SBB SBF SBG One Line
Updated
A PDF document (141 KB) attached to LEX Triannual Energy Study and ARC Flash Testing, from the Department of Veterans Affairs. Due Nov 30, 2027, 11:00 AM (UTC-6).
File name: Bowling Tower SWB SBB SBF SBG One Line.pdf
The full file is for paid members, or buy this bid alone.
Preview
KU Feeder Crt #136
(Used for equipment
duty calculations)
MAIN SVR #2
0.065303 + j0.423956
0.051187 + j0.323509
OPEN
KU Feeder Crt #119
( Used for Arc Flash
Calculations)
MAIN SVR 2 #119
0.06533 + j0.430291
0.051187 + j0.323509
3200A-(Generic)
CU, 15'
Fed from Tower Main Service #2
Transformers T-2 & T-3
kV
0.
1350A-(Generic)
AL, 300'
1350A-(Generic)
AL, 2'
1350A-(Generic)
AL, 20'
0.
kV
0.
kV
1-1/C-3/0 AWG
CU, 125', [Conduit]
kV
0.
1350A-(Generic)
AL, 2'
1-1/C-400 kcmil
CU, 105', [Conduit]
kV
1-1/C-2 AWG
Continue on SWB SBC
BusPlug BP CCU.
Sheet xxxxxxxxxx
1-1/C-3 AWG
CU, 5', [Conduit]
MTS-CCU
T-CCU
75 kVA
0.48 - 0.208 kV
2.8%
kV
Siemens QJH
225/200A
PNL CCU
BP T-PJ/PN
Shawmut TRS
100A
0. CU, 120', [Conduit]
kV
GE TB1
150/100A
1-1/C-3 AWG
CU, 10', [Conduit]
BP SPARE
PNL PR
BP LG-6TH FLR
1350A-(Generic)
AL, 2'
1-1/C-2 AWG
CU, 10', [Conduit]
BP T-PA/PD
1-1/C-2 AWG
CU, 85', [Conduit]
DC PA/PD
BUSS FRS-R(RK5)
100A
DC T-PNN PRI
kV
0.
T-PNN
45 kVA
0.48 - 0.208 kV
6.1%
BUSS FRS-R(RK5)
200A
GE TFJ
225/200A
1-1/C-3/0 AWG
CU, 10', [Conduit]
PNL 5HN
T-5LNA
75 kVA
0.48 - 0.208 kV
4.65%
1-1/C-3/0 AWG
CU, 75', [Conduit]
1-1/C-3 AWG
35', [Conduit]
0CU,
.4
kV
PNL 5LNA
Eaton EDB
225/200A
1-1/C-3/0 AWG
10', [Conduit]
0CU,
.2
kV
Eaton EDB
225/200A
0.
PNL LL
GE TEY
100/20A
PNL PNN
Eaton FD
225/125A
GE TB1
150/100A
PNL 5LNB
1-1/C-3/0 AWG
10', [Conduit]
0CU,
.2
kV
DC -T-PNN SEC
kV
BP LL
0.
kV
BP T-PL/PLA (PM)
kV
1350A-(Generic)
AL, 2'
kV
1-1/C-4/0 AWG
CU, 35', [Conduit]
PNL PLA
PNL PH
1-1/C-2 AWG
CU, 85', [Conduit]
1350A-(Generic)
AL, 2'
PNL PL
GE TQD
225/225A
0.
0.
kV
T-PL/PLA
75 kVA
0.48 - 0.208 kV
2.5%
BP 5HN
GE TQD
225/225A
0.
kV
Shawmut TRS
100A
Shawmut TRS
PNL PA
100A
1-1/C-2 AWG
CU, 10', [Conduit]
Siemens QJH
225/200A
GE TEY
100/20A
0.
kV
PNL PG
kV
BP T-PNN
1350A-(Generic)
AL, 20'
0.
Siemens QJH
225/200A
Siemens QJH
225/200A
PNL PD
1350A-(Generic)
AL, 2'
T-PA/PD
75 kVA
0.48 - 0.208 kV
2.5%
0.
kV
SQD QOB
125/20A
1-1/C-4/0 AWG
CU, 25', [Conduit]
1-1/C-2 AWG
CU, 10', [Conduit]
PNL PNA
T-PG/PH
112.5 kVA
0.48 - 0.208 kV
2.5%
1-1/C-4/0 AWG
CU, 10', [Conduit]
0.
Shawmut TRS
100A
DC T-PG/PH
0.
PNL PJ
Siemens BQD
100/100A
kV
Shawmut TRS(RK5)
150A~
1-1/C-1/0 AWG
CU, 60', [Conduit]
1350A-(Generic)
AL, 20'
kV
0.
Siemens QJH
225/200A
1-1/C-4/0 AWG
CU, 35', [Conduit]
Siemens QJH
225/200A
PNL PN
BP T-PG/PH
1-1/C-1/0 AWG
CU, 5', [Conduit]
T-PJ/PN
75 kVA
0.48 - 0.208 kV
The beginning of the document. Download the full file to read on.
Other documents in this bid
- Bid document
- Bid document
- Bid document
- Bowling B MV One Line
- Bowling Combined Arc Flash Project - Volume 2 Data Files
- Bowling Electrical Main Hospital One Line
- Bowling Electrical Risers
- Bowling ONE-LINE E-602-1
- Bowling Tests Summary
- Bowling Tower Gen 1 2 One Line
- Bowling Tower SWB SBA SBC SBD SBE SBH One Line
- Bowling VA Combined Test Report 2023