Home / LEX Triannual Energy Study and ARC Flash Testing / Document

Bowling ONE-LINE E-602-1

Updated

A PDF document (231 KB) attached to LEX Triannual Energy Study and ARC Flash Testing, from the Department of Veterans Affairs. Due Nov 30, 2027, 11:00 AM (UTC-6).

File name: Bowling ONE-LINE E-602-1.pdf

Download the full documentSee the bid

The full file is for paid members, or buy this bid alone.

Preview

CPLIT-1-A627

NPLIT-1-A627

SPD

SPD

M

M

SIXTH FLOOR

100-1

SIXTH FLOOR

A

100-1

SPD

SPD

M

FIFTH FLOOR

NPLIT-1-AU547

CPLIT-1-AU547

A

M

FIFTH FLOOR

CPLIT-1-A450

100-1

NPLIT-1-A450

100-1

SPD

SPD

M

FOURTH FLOOR

M

FOURTH FLOOR

NPLIT-1-A345

CPLIT-1-A345

100-1

100-1

THIRD FLOOR

SPD

SPD

M

M

THIRD FLOOR

NPLIT-1-A243

CPLIT-1-A243

100-1

100-1

B

SPD

M

SECOND FLOOR

B

SPD

M

SECOND FLOOR

CPLIT-1-A104 CPLIT-1-B125

NPLIT-1-A104 NPLIT-1-B125

100-1

100-1

FIRST FLOOR

SPD

SPD

SPD

SPD

M

M

M

M

100-1

FIRST FLOOR

CRAC-2 INDOOR

100-1

CPLIT-1-B046 CPLIT-1-A002C

ECDP1

CRAC-2 OUTDOOR

UPS-LDC

UPS-1

UPS-2

UPS-MBC-TC

NPLIT-1-B046 NPLIT-1-A002C

400-1

M

SPD

M

DATA CENTER

NEW UPS-B

SPD

SPD

M

M
400A
350A

400A
350A

50A

15A

DC LDC

BUS DUCT CONTINUES

400A
350A

400A
350A

L

H2 480/277V 400A

ATS-UPS

250A

200A
NF DISC.

150A

DC UPS-1

DC UPS 2

DC MBP-TC

DATA CENTER

UPS-B BYPASS

200-2

100-1

N

C

T-1-EC
112.5 kVA

T-EL

CRAC-1

INDOOR

CRAC-3

INDOOR

CRAC-1

OUTDOOR

C

CRAC-3

OUTDOOR

E
SPD

M

200-2
400A
MCB

100A

100A

100A

100A

100A

100A

60A

200-2

200-2

SPD

100A

60A

M
M

ECDP-1

208/120V 400A

(BUILDING 1 - TR CRITICAL POWER)

400-1

M

400AF
200AT
LSI

400A
MCB

100A

100A

100A

100A

100A

100A

60A

60A

60A

M

250AF
175AT
LSI

NDP-1 208/120V 400A

400-1

400AF
200AT
LSI

T-UPS 2

112.5 kVA

T-UPS 1

112.5 kVA

DC T-UPS 2

DC T-UPS 1

T-A

15A

15A
ELC

(BUILDING 1 - TR NORMAL POWER)

100 A

250A
250A

250A
250A

T-1-NP
112.5 kVA

225 A

EH1 480/277V 400A

M

DATA CENTER NEW UPS-A

T-1-EC

50A

100 A

HCDP1-EHRM

600A 480/277V

CRITICAL POWER

BUS DUCT RISER

50A

30A

150A

200-2

225 A

T-CPH

MCB

T-CPK

T-PPP

T-SBK

T-SBL

T-PEE

LG

T-PDD

LE-1

200A
NF DISC.

SBJ

HEMG

DATA CENTER

UPS-A BYPASS

HEMG-1

T-EPB

600A BUS DUCT RISER

SPD

200-2

200-2

200-2

New breaker located
inside of SBC

D

M
600AF
480AT
L,S

1600AF
1280AT
L,S,I

300AF
210AT
L,S

600AF
300AT
L,S

600AF
600AT

1600AF
800AT
L,S, I

800AF
400AT
L,S, I

400AF
165AT
L,S, I

400AF
560AT
L,S

800AF
920AT
L,S

L

2000AF
2000AT
L,S

SBC

Critical
ATS

M

M
250AF
175AT
LSI

400AF
200AT
LSI

600AF
600AT

M

D

400AF
200AT
LSI

600AF
210AT

600AF
160AT

600AF
200AT

1600AT
800AF

HNDP1-EHRM

600A 480/277V

N

SBB

SBE

E
L

ATS-EQUIP

MCC

LF

MCA

T-PFF

T-PCC

N
E

FIRE PUMP

MOTOR

ATS CRITICAL

DPLS

1600AF
1600AT
L,S

SBG

SBF

1600AF
800AT
L,S

1600AF
1600AT
L,S

400A

E

600AF
600AT
L,S,I

SBH

L
N
N
E

T4
1500 kVA

800AF
600AT
L,S,I

NOT TO SCALE

1600AF
1000AT
L,S,I

T3
1000 kVA

T2
1000 kVA

T1
1500 kVA

400AF
400AT
L,S,I

TOWER BLDG 1 MV SWG BUS 1

TOWER BLDG 1 MV SWG BUS 2

F
1600AF
1520AT
L,S,I

TEMP

GENERATOR

1600AF
1520AT
L,S,I

1600AF
1520AT
L,S,I

G

GENERATOR #2

1000 kW
1250 kVA

The beginning of the document. Download the full file to read on.

Other documents in this bid