KU Feeder Crt #136
(Used for equipment
duty calculations)

MAIN SVR #1

0.072872 + j0.442181
0.08063 + j0.394066

OPEN

KU Feeder Crt #119
( Used for Arc Flash
Calculations)

MAIN SVR 1 #119

0.0729 + j0.448353
0.08063 + j0.394066

3200A-(Generic)
CU, 25'

Fed from Tower Main Service #1
Transformers T-1 & T-4

1200/5

GE AK-3-75

3000/2100A

50 HP

Induction
16.7%

AHU-6W SF

1-1/C-8 AWG

PNL CPL PH

Siemens ED6
125/25A

SQD EDB

125/40A

1-1/C 1 AWG

CU, 15' [Conduit}

Refer to SWB SBH for
continuation to ATS

ELEV S4

Refer to SWB SBH for
continuation to ATS
ELEV 4 (P2).

Sheet xxxxx

Sheet xxxx

1350A-(Generic)
AL, 240'

1-1/C-2 AWG

80', [Conduit]
0CU,
.4
kV

1350A-(Generic)
AL, 80'

1-1/C-3 AWG

CU, 5', [Conduit]

1350A-(Generic)
AL, 2'

1-1/C-3/0 AWG

3-1/C-350 kcmil
CU, 35', [Conduit]

kV
0.

GE TEY

100/20A

0. CU, 10', [Conduit]

kV

T-EPA

30 kVA

0.48 - 0.208 kV

2.5%

Siemens BLH
125/20A

GE SGLC04

400/150A

T-PH

75 kVA

0.48 - 0.208 kV

5.5%

1-1/C-1 AWG

CU, 15', [Conduit]

150 HP
Induction
16.7%

40 HP

Induction
16.7%

DC T-ELEV 5 P3

1-1/C-1 AWG

CU, 15', [Conduit]

T-ELEV 3 (P1)

63 kVA

0.48 - 0.48 kV

4.8%

1-1/C-1 AWG

CU, 15', [Conduit]

kV
0.

kV
0.

Siemens HHJXD6-A
400/350A
200 HP
Induction
16.7%

200 HP
Induction
16.7%

T-ELEV 4 (P2)

63 kVA

0.48 - 0.48 kV

4.8%

40 HP

Induction
16.7%

ELEV #4 (P2)

AHU-5

AHU-6

AHU-7

Siemens HEB
125/50A

T-EP1

30 kVA

0.48 - 0.208 kV

4.5%

Siemens HBL
125/100A

PNL EP1

T-ELEV 5 (P3)

63 kVA

0.48 - 0.48 kV

4.8%

40 HP

Induction
16.7%

ELEV #5 (P3)

kV

1-1/C-1 AWG

0. CU, 15', [Conduit]

kV

kV

DC TELEV2 SEC S5

40 HP

Induction
16.7%

Siemens HHJXD6-A
400/300A

Siemens HFXD6
250/250A

1-1/C-1 AWG

CU, 15', [Conduit]

0.

1-1/C-1 AWG

CU, 15', [Conduit]

kV

kV
0.

Shawmut TRS(RK5)
100A

1-1/C-1 AWG

CU, 15', [Conduit]

DC T-ELEV 4 P2

T-ELEV 2 (S5)

63 kVA

0.48 - 0.48 kV

4.9%

PNL PH

ATS- ELEV 5 (P3)

0.

1-1/C-1 AWG

CU, 5', [Conduit]

1-1/C-1 AWG

CU, 15', [Conduit]

DC T-ELEV 3 P1

Siemens QJH2
225/225A

0.

DP SBO

1-1/C-1 AWG

CU, 40', [Conduit]

1-1/C-1 AWG

CU, 5', [Conduit]

1-1/C-1 AWG

0. CU, 5', [Conduit]

kV

1-1/C-1 AWG

CU, 90', [Conduit]

1-1/C-1 AWG

CU, 5', [Conduit]

2-1/C-350 kcmil
CU, 50', [Conduit]

Sheet xxxxx

1-1/C-6 AWG

CU, 30', [Conduit]

1-1/C-1 AWG

CU, 90', [Conduit]

Refer to SWB SBE for
continuation to DP SBM.

ATS- ELEV 4 (P2)

1-1/C-1 AWG

CU, 15', [Conduit]

0. CU, 15', [Conduit]

kV

1-1/C-6 AWG

0.

kV

GE TB4

400/125A

GE SGLC06

600/600A

GE SGLC04

400/150A

1-1/C-1 AWG

CU, 60', [Conduit]

GE SGLC04

400/150A

The beginning of the document. Download the full file to read on.