Bowling Tower Gen 1 2 One Line
Updated
A PDF document (112 KB) attached to LEX Triannual Energy Study and ARC Flash Testing, from the Department of Veterans Affairs. Due Nov 30, 2027, 11:00 AM (UTC-6).
File name: Bowling Tower Gen 1 2 One Line.pdf
The full file is for paid members, or buy this bid alone.
Preview
GEN #2 TOWER
1250 kVA
14.8%
26.7%
0.022%
C-H DSII-608
800/400A
1200/5
R
C-H DSII-608
800/800A
DC ATS FIRE PUMP
C-H DSII-616
1600/400A
Feed from SWB SBA
R
1200/5
Sheet xxxxx
SWB SBA
0.080305 + j0.419855
0.610845 + j0.70511
1350A-(Generic)
CU, 105'
Shawmut TRS
600A
C-H DSII-616
1600/1600A
1200/5
R
KU Feeder Crt #136
(Used for equipment
duty calculations)
0.
1-1/C-350 kcmil
CU, 25', [Conduit]
1200/5
C-H DSII-616
1600/1520A
C-H DSII-616
1600/1520A
1350A-(Generic)
CU, 85'
Assumed all BGFL
settings
kV
SWB ESB
R
kV
C-H DSII-616
1600/1120A
1200/5
R
0.
1200/5
R
To ATS-CRITICAL
To ATS-EQUIP
Sheet Tower
Sheet Tower
KU Feeder Crt #119
( Used for Arc Flash
Calculations)
SWB SBA CRT #119
0.080379 + j0.425267
0.610845 + j0.70511
OPEN
SWB SBA
R
GE AKS-50
1600/400A
1-1/C-500 kcmil
CU, 80', [Conduit]
1200/5
4-1/C-350 kcmil
CU, 40', [Conduit]
4-1/C-500 kcmil
CU, 50', [Conduit]
TEMP GEN
1-1/C-500 kcmil
CU, 70', [Conduit]
To Fire Pump ATS
ATS LS
1-1/C-500 kcmil
CU, 10', [Conduit]
Sheet MV
0.
kV
GE SGLA 3P
PNL DPLS
PNL PLSH
PNL PLSG
PNL PLSE
PNL PLSC
0.
kV
1-1/C-2 AWG
CU, 420', [Conduit]
1-1/C-4 AWG
CU, 85', [Conduit]
kV
0.
1-1/C-1/0 AWG
10', [Conduit]
0CU,
.2
kV
1-1/C-6 AWG
CU, 15', [Conduit]
PNL PLSA
Siemens BL
125/60A
kV
kV
1-1/C-4 AWG
CU, 15', [Conduit]
Siemens BLH
125/70A
0.
0.
GE THHQB
100/50A
T-CPP
30 kVA
0.48 - 0.208 kV
4.8%
T-PLSA
PNL CPP
30 kVA
0.48 - 0.208 kV
4.8%
0.
T-PLSB
30 kVA
0.48 - 0.208 kV
4.8%
kV
1-1/C-2 AWG
CU, 25', [Conduit]
PNL PLSB
GE TEY
100/45A
1-1/C-6 AWG
CU, 25', [Conduit]
kV
DC T-PLSA PRI
1-1/C-6 AWG
CU, 20', [Conduit]
kV
0.
GE THHQB
100/50A
GE
60 A
0.
1-1/C-6 AWG
CU, 10', [Conduit]
kV
0.
1-1/C-2 AWG
CU, 10', [Conduit]
GE THHQB
100/50A
T-PLSC
30 kVA
0.48 - 0.208 kV
4.8%
PNL LSA
GE TEY
100/30A
DC T-PLSB PRI
1-1/C-6 AWG
CU, 10', [Conduit]
kV
T-PLSD
30 kVA
0.48 - 0.208 kV
4.8%
GE
60 A
GE SELA 3P
1-1/C-2 AWG
CU, 15', [Conduit]
PNL LSB
1-1/C-2 AWG
400', [Conduit]
0CU,
.4
kV
GE SELA 3P
GE TEY
100/45A
1-1/C-6 AWG
CU, 125', [Conduit]
kV
1-1/C-6 AWG
CU, 10', [Conduit]
1-1/C-2 AWG
CU, 10', [Conduit]
PNL PLSD
GE
60 A
0.
1-1/C-6 AWG
CU, 10', [Conduit]
kV
kV
GE THHQB
100/50A
1-1/C-6 AWG
400', [Conduit]
0CU,
.4
kV
1-1/C-6 AWG
390', [Conduit]
0CU,
.4
kV
PNL LSC
DC T-PLSC PRI
0.
kV
GE THHQB
100/50A
0.
1-1/C-2 AWG
CU, 10', [Conduit]
T-PLSE
30 kVA
0.48 - 0.208 kV
4.8%
GE SELA 3P
GE TEY
100/45A
DC T-PLSD PRI
1-1/C-6 AWG
CU, 10', [Conduit]
1-1/C-6 AWG
CU, 10', [Conduit]
PNL PLSF
GE
60 A
0.
1-1/C-6 AWG
CU, 10', [Conduit]
The beginning of the document. Download the full file to read on.
Other documents in this bid
- Bid document
- Bid document
- Bid document
- Bowling B MV One Line
- Bowling Combined Arc Flash Project - Volume 2 Data Files
- Bowling Electrical Main Hospital One Line
- Bowling Electrical Risers
- Bowling ONE-LINE E-602-1
- Bowling Tests Summary
- Bowling Tower SWB SBA SBC SBD SBE SBH One Line
- Bowling Tower SWB SBB SBF SBG One Line
- Bowling VA Combined Test Report 2023