FAULT CURRENT SCHEDULE

REF.

POINT

A

B

DESCRIPTION

EM BUSWAY

205 MDP

LATS-EM

LATS-NORM

GLS1
1LS1
1LS2

CATS-EM

CATS-NORM

CDP
GC1
1C1
1C3
MVP-1

N-ATS-EM

N-ATS-NORM

NDP
GN1
GN2
1N1
1N2
1N3
1N4

EQ-ATS-EM

EQ-ATS-NORM

EQDP

GEQ1
1EQ1

ELEV-1

ACCU-205-G

ACCU-205-1

ACCU-203-1

EHU-205-G

EHU-205-1
EHU-203-1

AHU-205-GRF

AHU-205-GSF

AHU-205-1RF

AHU-205-1SF

AHU-203-1RF

AHU-203-1SF

MIN. EQUIP.

RATING

10kAIC

42kAIC

42kAIC

42kAIC

24kAIC

10kAIC

10kAIC

42kAIC

42kAIC

42kAIC

24kAIC

24kAIC

10kAIC

10kAIC

42kAIC

42kAIC

42kAIC

24kAIC

24kAIC

18kAIC

18kAIC

10kAIC

10kAIC

42kAIC

42kAIC

42kAIC

20kAIC

10kAIC

10kAIC

5kAIC

5kAIC

5kAIC

5kAIC

5kAIC

5kAIC

5kAIC

5kAIC

5kAIC

5kAIC

5kAIC

5kAIC

ELECTRICAL SING LE-LINE LEGEND

FEEDER SCHEDULE

AVAILABLE SHORT

CIRCUIT AMPS

8,034
32,042
7,536
24,834
19,691
8,986
3,394
7,805
28,643
25,790
17,222
10,510
3,508
5,344
7,805
28,623
25,757
17,205
17,195
10,504
10,498
3,507
3,496
7,898
29,895
27,841
17,881
3,519
6,222
3,585
3,578
3,024
1,452
1,438
1,356
1,447
2,257
1,001
3,562
1,447
3,562

NOTES:

REFER TO MOTOR SCHEDULE OR PANEL SCHEDULE FOR FEEDER SIZE

15 KV EPR 3 - #2/0 CU., 1 - #1 CU. GND. 600V, IN 4" C.
2000A: 5 SETS 4 - 600 kCMIL CU., IN 4"C.
1600A: 4 SETS 4 - 600 kCMIL CU., 1 - #4/0 CU. GND., IN 4"C. 800A: 2 SETS OF 4 - 500 kCMIL CU., 1 - #1/0 CU. GND., IN 4"C. 600A: 2 SETS OF 4 - 350 kCMIL CU., 1 - #1 CU. GND., IN 3"C. 400A: 4 - 500kCMIL CU., 1 - #3 CU. GND., IN 4"C.
225A: 4 - #4/0 CU., 1 - #4 CU. GND., IN 2.5"C.
100A: 4 - #2 CU., 1 - #8 CU. GND., IN 1.25"C.

CONDUIT & W IRE

1. PROVIDE NEW MEDIUM VOLTAGE FUSE IN EXISTING PAD-MOUNTED GEAR.

CONDUIT & W IRE TO BE REMOVED

2. CONTACTS FOR LOAD BANK DUMP CIRCUITRY.

EXISTING CONDUIT & W IRE TO REMAIN

A

INTEGRATED EQUIPMENT ENCLOSURE

3. LOAD BANK DUMP BOX.

SW ITCHBOARD ENCLOSURE

4. PROVIDE GROUNDING FOR SEPERATELY DERIVED SYSTEM.

BUSSING

N

AUTOMATIC TRANSFER SW ITCH

E

AUTOMATIC TRANSFER SW ITCH - BYPASS

E

N
N

REMOVABLE

BUS LINK

G

BUS LINK

DELTA SYMBOL

DISCONNECT

M

ELECTRIC METER

A

EQUIPMENT AMMETER

B

EQUIPMENT CURRENT TRANSFORMER

EQUIPMENT GROUND

M

EQUIPMENT MULTIMETER

EQUIPMENT POTENTIAL TRANSFORMER

SW BD

METERING

FROM EXISTING

TRANSFORMER PMT-9

EQUIPMENT SW ITCHBOARD METER

EQUIPMENT W YE SIDE OF TRANSFORMER W ITH GROUND

G

GENERATOR

GROUND FAULT PROTECTOR

GFP

EXISTING PAD MOUNTED SWITCH

C

60E

KEYED INTERLOCK

K

PRIMARY SW ITCH

EXISTING LOAD - 398kVA (32A AT 12.47kV)

NEW LOAD - 375kVA (30A AT 12.47kV)

MOTOR

TOTAL - 773kVA (62A AT 12.47kV)

The beginning of the document. Download the full file to read on.