ABB
MV SWITCHGEAR TEST
CERTIFICATION REPORT
Mebane - MV Switchgear
JOB FILE INFORMATION ENTRY FORM
CUSTOMER NAME: FGC CONSTRUCTION LLC
END USER: SLAC
CUSTOMER PURCHASE ORDER NUMBER:
REVISION/CHANGE ORDER LEVEL:
1173
APPARATUS SERIAL NUMBER: 1VAL3149A01
D
R
AF
T
SAP Shop Order Number
152933518-0010
ABB SHOP ORDER NUMBER: CS03149A01
REMARKS:
DATE OF MFG (MO/YR):
1VAM-T0005-900015 Rev. G
Approver: Quality Manager
Jul-25
MV SWITCHGEAR TEST
CERTIFICATION REPORT
ABB
APPARATUS SERIAL NO:
1VAL3149A01
CUSTOMER: FGC CONSTRUCTION LLC
ABB SHOP ORDER #:
CS03149A01
END USER:
SLAC
CUSTOMER PO:
1173
REVISION:
The above equipment was tested and found satisfactory in conformance with IEEE C37.20 series of Metal-clad or Metal-Enclosed switchgear standards, specifically those sections pertaining to production tests.
MECHANICAL TESTS:
Physical tests and inspections were conducted to assure conformance with drawing requirements and manufacturing specifications.
AF
T
Switchgear structures were tested to assure proper functioning of shutters, interlocks, disconnect contacts, etc., and were gauged to assure uniformity of the structure and interchangeability of circuit breaker elements.
ELECTRICAL TESTS:
Instrument, relay, heaters and control wiring, together with their connected devices, were functional and operated at normal rated current and/or voltage and proper performance of the devices demonstrated.
R
When provided, grounding of metal case and/or frames of instrument transformers, to the switchboard ground bus, was verified by a voltage test of 10v or less.
D
Sequential operation of devices so connected was tested per the Elementary and/or Schematic diagrams and found satisfactory.
Continuity check of all circuit wiring was performed to verify conformance to circuit diagrams. Manually operated circuit breakers were operated and checked for proper function. Dielectric testing was performed in accordance with the requirements of IEEE C37.20 series, with no failures.
This is to certify that the items and services comply with the applicable specification, purchase order, and drawing requirements. Final testing of the apparatus was performed as described in the attached Test Document and indicates full conformance with the requirements of the Purchase Order.
SUE OLMOS
Authorized QA Representative
Electrification Distribution Solutions
6801 Industrial Dr. Mebane, NC 27302
8/13/2025
Date
ABB
Phone 919-563-5561
1VAM-T0005-900015 Rev. G
Approver: Quality Manager
MV SWITCHGEAR TEST
CERTIFICATION REPORT
ABB
APPARATUS SERIAL NO:
The beginning of the document. Download the full file to read on.
Other documents in this bid
- Draft B2 00 Cover Letter
- Draft B2 01 Request for Proposals Section A (Subcontract Form)
- Draft B2 02 Request for Proposals Section B (Supplies or Services and Price Costs
- Draft B2 03.00 Request for Proposals Section C (Specifications Statement of Work)
- Draft B2 03.01 Statement of Work
- Draft B2 03.03 Commissioning Plan
- Draft B2 03.04 CUIR Subproject 1 Power Outages and Linac Downtime Plan
- Draft B2 03.05 CUIR's Quality Requirements for Subcontractors
- Draft B2 03.06 Department of Energy Order 414.1E Quality Assurance
- Draft B2 03.08 00 Appendix I Technical Data Submittal
- Draft B2 03.09 01 Packaging Procedure MV Switchgear Shipping Preparation-2
- Draft B2 03.13 Certificate of Conformity